VCB-X Controllers

VCB-X Miscellaneous & Relays Setpoints

Outdoor Sensor Calibration Offset

If the Outdoor Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Enter a positive Sensor Calibration value to raise the
Outdoor Air Temperature Sensor reading and a negative value to lower
the Sensor reading. High limit = 100ºF / 55.5ºC; Low limit = -100ºF /
-55.5ºC; Default = 0ºF / 0ºC.

Return Sensor Calibration Offset

If the Return Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset reading to adjust the Sensor’s Sensi-
tivity. Enter a positive Sensor Calibration value to raise the Return Air
Temperature Sensor reading and a negative value to lower the Sensor
reading. High limit = 100ºF / 55.5ºC; Low limit = -100ºF / -55.5ºC;
Default = 0ºF / 0ºC.

Coil Temperature Calibration Offset

If the Coil Temperature Sensor is reading incorrectly, you can use this
option to enter an offset reading to adjust the Sensor’s Sensitivity. Enter
a positive Sensor Calibration value to raise the Coil Temperature Sensor
reading and a negative value to lower the Sensor reading. High limit
= 100ºF / 55.5ºC; Low limit = -100ºF / -55.5ºC; Default = 0ºF / 0ºC.

Relays Setpoints

Touch the

< Relays>

button to access the Outputs Setpoints

Screens. Touch the radio button next to the desired relay
selection. Choose one relay output from each screen for
Relays 2 through 23 depending on whether you have the

EM1 Module and/or 12 Relay Module installed and confi gured. See
Table 7 on the next page for Relay Defi nitions.

NOTE:

Relay #1 is not confi gurable as it is reserved for the

Supply Air Fan.



Not Used

 

Digital Compressor

 

Cooling Stage

 

Heating Stage

 

Condenser Fan

 

Heat Pump Compressor

 

Heat Pump Reversing Valve

 

Heat Pump Aux Heat

 

Heat Pump Emergency Heat

 

Mod Heat Enable

 

Mod Cool Enable

 

Morning Warm Up

 

Reheat

 

Preheat

 

Low Ambient

 

Exhaust Fan

 

Economizer

 

Heat Wheel

 

Occupied Mode

 

Override Mode

 

Alarm Indicator

Relays