PROGRAMMING TABLE
Command
Code
Programming Command Description
Command
Syntax
Factory
Setting
New
Setting
10
Set loop response time #1
40 Milliseconds to 10.2 Seconds, 001 = 40 mS
10 [DATA] #
001
40 mS
11
Set loop response time #2
40 Milliseconds to 10.2 Seconds, 025 = 1000 mS (1 Sec)
11 [DATA] #
025
1000 mS
12
Change PAC (Program Authorization Code)
1 to 6 Digits
12 [DATA] #
987654
13
Change Operate Key Code
1 to 6 Digits
13 [DATA] #
11
14
Change Password
1 to 6 Digits
14 [DATA] #
321
15
Change unit address
1 to 4 Digits
15 [DATA] #
0000
16
Set arm delay
000 to 255 Seconds
16 [DATA] #
015
Seconds
17
Set telephone dial delay after alarm
000 to 255 Seconds
17 [DATA] #
005
Seconds
18
Set alarm cutoff
000 to 255 Seconds
18 [DATA] #
030
Seconds
19
Set alarm delay
000 to 255 Seconds
19 [DATA] #
015
Seconds
20
Set password error counter
00 to 15 Errors, 00 = Disable counter
20 [DATA] #
02
Errors
21
Set communication dial attempts
00 to 15 Attempts, 00 = No communication attempts
21 [DATA] #
08
Attempts
22
Set telephone number 1
1 to 32 Digits
22 [DATA] #
None
23
Set telephone number 2
1 to 32 Digits
23 [DATA] #
None
24
Select speech message buffer to update
Buffer address 00 through 15
24 [DATA] #
00
Buffer 0
25
Change speech message data
Word Address 00 through 15
Word 000 through 255
25 <WORD ADDRESS> [WORD] #
See Section
4.4.15
26
Select sign on message
Message buffer 00 through 15
26 [DATA] #
02
Buffer 2
27
Set ring counter for off hook
00 to 15 Rings
00=Disable counter or 15 rings with program switch on
27 [DATA] #
04
Rings
28
Select alarm message delay
Select 0 to 3, 0=None, 1=5 Sec., 2=15 Sec., 3=30 Sec.
28 [DATA] #
1
5 Seconds
29
Reserved for future use