REMKO RXW 350 User Manual

Page 8

Advertising
background image

8

Timer buttons
T-ON / T-OFF

The unit is programmed to automatically switch on or off with this button. By pressing the T-
ON / T-OFF button, the timer is activated and the time display disappears. The timer sym-
bol ON or OFF time blinks. By pressing the TEMP UP/DN button, the desired timer on or off
time is set. Once the setting is made, the respective timer button has to be pressed again.
The display of the indoor unit is lit up.
If the programmed time is reached, the unit automatically switches on or off. If the indoor
unit automatically switches on, the last mode, temperature and fan speed setting is acti-
vated.
To disable the timer on or off function prior to its activation time, press the CANCEL button.
The display of the indoor unit is not lit up.

Functional process

T-ON button
Delayed start

SWING button

The oscillating function of the air outlet fins is set with this button. To directly position the air
outlet fins, this button must be pressed again. The swing function improves the air distribu-
tion in the room.

Functional process

SWING

SWING

SLEEPING button

With this button, a program is activated that increases the target temperature by 1°C after
one hour and 2°C after two hours when the unit is in cooling mode. In heating mode, the
target temperature is decreased by 1°C after one hour and by 2°C after two hours. The dis-
play of the indoor unit is not lit up.

Functional process

SLEEPING

SLEEPING

Heating mode

In heating mode, you can heat the room in spring and autumn. The selected room tempera-
ture is set in 1°C increments with the TEMP UP/DN button. If the room temperature falls 1°
C below the selected target temperature, the indoor unit begins to heat the room air. If the
adjusted room temperature falls approx. 0.5°C and the compressor’s minimum term of
6 minutes is transgressed, the control mechanism switches cooling mode off.
To protect the compressor, the control mechanism only reactivates heating mode after
3 minutes have elapsed.

Functional process

HEATING MODE

MODE

T-OFF button
Delayed stop

T-ON

TEMP UP/DN

Delayed
start

T-ON

T-OFF

TEMP UP/DN

T-OFF

Delayed
stop

Advertising