Technical Service Diagnosis

July 1999

Page 19

CSW45

Symptom

Probable Cause

Possible Correction

Low ice making capacity

Dirty air cooled condenser

Clean condenser coil

Dirty fan blade

Clean fan blade

Water valve does not shut off
tightly

Check/replace inlet water valve

Scale on the evaporator surface

Clean the ice machine’s water
system

Unit in a very warm room

Less ice will be made in
temperatures over 90

o

F.

Unit will not shut off

Ice level control failure

Check to see if it is unplugged
from the control box, if its
plugged in, check resistance
levels given on next page

Ice size incorrect

Evaporator thermistor failure

Check to see if it is unplugged
from the control box, if its
plugged in, check resistance
levels given on next page

Ice formation uneven

Water distributor restricted

Clean the ice machine’s water
system

Cutter grid failure

Replace grid

Makes excessive noise

Components contacting

Check & adjust position of tubes
and panels

Fan blade bent

Check & replace fan blade

Fan or pump motor bearing
failure

Locate noise, unplug motor to
confirm. Replace worn
component.

Water in bin

Drain plugged

Clean out drain

Drain pump failed

Check/replace pump

Ice melted together

Low amount of ice used

Remove ice