11

A. Suppose that the Proportional Bandwidth Potentiometer (R14) was set to 0.6 volts to

just sustain a temperature oscillation. (Reference sections 12.5 and 12.6).


B. It was then observed that the natural period of this oscillation was 2 minutes.

(Reference section 12.7)

C. The Proportional Bandwidth Potentiometer (R14) should be adjusted so the voltage at

TP4 is equal to 1.2 volts. (Reference section 12.8 and the “Proportional Bandwidth as
a Function of Voltage
” graph.)

D. The Integral Rate Potentiometer (R16) should be set to the inverse of the natural

period. This is 1/(2 min) = 0.5 repeats per minute. The potentiometer should be
adjusted until TP5 is at 0.98 volts. (Reference section 12.9 and the “Integral Rate as a
Function of Voltage”
graph.)