Fireplace installation – Desa (V)KC36NE Series User Manual

Page 22

Advertising
background image

www.desatech.com

116238-01E

22

Figure 30 - External Regulator with Vent

Pointing Down (Propane/LP Only)

Propane/LP
Supply Tank

External
Regulator

Vent
Pointing
Down

CAUTION: Use only new,

black iron or steel pipe. Inter-

nally-tinned copper tubing may

be used in certain areas. Check

your local codes. Use pipe of

1/2" diameter or greater to allow

proper gas volume to fireplace.

If pipe is too small, undue loss

of volume will occur.

Installation must include an equipment shutoff

valve, union and plugged 1/8" NPT tap. Locate

NPT tap within reach for test gauge hook up.

NPT tap must be upstream from fireplace (see

Figure 31).
IMPORTANT

: Install main gas valve (equipment

shutoff valve) in an accessible location. The main

gas valve is for turning on or shutting off the gas

to the appliance.

Check your building codes for any special re-

quirements for locating equipment shutoff valve

to fireplaces.

Apply pipe joint sealant lightly to male NPT

threads. This will prevent excess sealant from

going into pipe. Excess sealant in pipe could result

in clogged fireplace valves.

WARNING: Use pipe joint

sealant that is resistant to liquid

petroleum (LP) gas.

FIREPLACE

INSTALLATION

Continued

We recommend that you install a sediment trap/

drip leg in supply line as shown in Figure 31. Lo-

cate sediment trap/drip leg where it is within reach

for cleaning. Install in piping system between fuel

supply and fireplace. Locate sediment trap/drip leg

where trapped matter is not likely to freeze. A sedi-

ment trap traps moisture and contaminants. This

keeps them from going into fireplace gas controls.

If sediment trap/drip leg is not installed or is in-

stalled wrong, fireplace may not run properly.

Figure 31 - Gas Connection

CSA Design-Certified
Equipment Shutoff Valve
with 1/8" NPT Tap*

3" Minimum

Approved
Flexible
Gas Line

Cap Pipe Tee Joint
Nipple

Sediment Trap/

Drip Leg

Natural - From
Gas Meter (5.5"
W.C. to 10.5" W.C.
Pressure)
Propane/LP From
External Regulator
(11" W.C. to 14"
W.C. Pressure)

* The CSA design-certified equipment shutoff

valve may be supplied with the appliance or you

can purchase it from your retailer.

CONNECTING FIREpLACE TO GAS
SUppLY

Installation Items Needed

• 5/16" hex socket wrench or nut-driver

• sealant (resistant to propane/LP gas, not

provided)

1. Open lower louver door panel by gently pull-

ing forward.

2. Route flexible gas line (provided by installer)

from equipment shutoff valve to fireplace.

Route flexible gas supply line through one of

the access holes on side of fireplace.

3. Attach flexible gas line from gas supply to

control valve (see Figure 32, page 23).

4. Check all gas connections for leaks. See

Checking Gas Connections, page 23.