Troubleshooting – Desa (V)KC36NE Series User Manual

Page 32

Advertising
background image

www.desatech.com

116238-01E

32

OBSERVED PROBLEM

Pilot will not stay lit

No gas to burner, although wall

switch and valve are set to the

ON position

Frequent pilot outage

Fireplace produces a clicking/tick-

ing noise just after burner is lit

or shut off

Slight smoke or odor during initial

operation

REMEDY

1. Check wiring connection.

Refer to wiring diagram (see

Wiring Diagram, page 27)

and/or check ground wire to

ignition module

2. Clean and adjust pilot burner

and check gas supply and inlet

pressure to unit

Note:

Have a qualified techni-

cian replace pilot assembly if

broken or corroded

1. Check electrical connections

1. Clean and adjust pilot flame for

maximum flame impingement

on thermopile

2. Have the vent system inspect-

ed, including the termination

cap. Remove any restriction

or obstruction

1. This is normal with most

fireplaces. If noise is exces-

sive, contact qualified service

person

1. Problem will stop after a few

hours of operation

TROUbLEShOOTING

Continued

POSSIBLE CAUSE

1. Loose wiring on ignitor wire

to ignition module and/or

poor ground to ignition mod-

ule

2. Pilot flame too low to sense

1. Wall switch wires defective

or too long

1. Pilot flame may be too

low, causing safety pilot to

“drop out”

2. Improper venting or excessive

blockage

1. Metal expanding while heating

or contracting while cooling

1. Residues from manufacturing

processes and logs curing