About Advanced Features & Operation

Page 18

CLOCK BACKUP - In the event of a power
thermostat’s internal clock will continue to keep
proper time for a minimum of 48 hours without
external power or batteries. The T0051FS stores
the time at which power is removed and resumes
timekeeping from that point, upon power restoration.


loss, the

2 STAGE OPERATION - The 2nd Stage of Heat or Cool is
turned on when (1) the 1st Stage has been on for a
minimum of two minutes, and (2) the temperature spread
from the setpoint is equal to or greater than: the setpoint
plus the deadband, plus 2 degrees.

Heat

Setpoint

Cool

Setpoint

Dead
Band

Dead
Band

2 degrees

2 degrees

1st Stage

turn on

Fan-Low

2nd Stage

turn on

Fan-Medium

1st Stage

turn on

Fan-Low

2nd Stage

turn on

Fan-High

Heating

Cooling

MINIMUM HEAT/COOL SETPOINT DIFFERENCE - The Heat
and Cool setpoints will not be allowed to come any closer
to each other than the value set in Advanced Setup step
# 16, on page 16. This minimum difference is enforced
during Auto-changeover and Program On operation.

DRY CONTACT SENSE - N.O.=Normally Open. N.O. setting
with dry contact closure enforces unoccupied settings
from normal operation. N.C.=Normally Closed. N.C.
setting with dry contact closure enforces normal operation
from unoccupied settings. This dry contact works in all
modes but OFF.