Installation, Continued, Mantel clearances – Desa CDR3924NT User Manual

Page 10: Floor clearances

Advertising
background image

www.desatech.com

113183-01D

10

INSTALLATION

Continued

Minimum

Noncombustible

Material

8"

Min.

12" 15" 18"

All minimum

distances are

in inches

20"

2

1/2

"

6"

8"

10"

12"

Distances to

Underside of

Mantel

Hood

(GA6050,

GA6052 or

GA6053)

Top of

Fireplace

Opening

Underside

of Mantel

Shelf

Mantel Shelf

MANTEL CLEARANCES

In addition to meeting noncombustible material

clearances, you must also meet required clearances

between fireplace opening and mantel shelf. If

you do not meet the clearances listed below, you

will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel

shelf and top of fireplace opening, a hood is not

required (see Figure 6).
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6 are not met, you

must have a hood. When using a hood there are

still certain minimum mantel clearances required.

Follow minimum clearances shown in Figure 7

when using hood.

NOTICE: Surface temperatures

of adjacent walls and mantels

become hot during operation.

Walls and mantels above the

firebox may become hot to

the touch. If installed properly,

these temperatures meet the

requirement of the national

product standard. Follow all

minimum clearances shown in

this manual.

NOTICE: If your installation does

not meet the minimum clear-

ances shown, you must do one

of the following:

• operate the logs only with the

flue damper open

• raise the mantel to an accept-

able height

• remove the mantel

FLOOR CLEARANCES

A. If installing appliance on the floor level, you

must maintain the minimum distance of 14"

to combustibles (see Figure 8).

B. If combustible materials are less than 14" to

the fireplace, you must install appliance at

least 5" above the combustible flooring (see

Figure 9).

Figure 6 - Minimum Mantel Clearances

Without Using Hood

Figure 8 - Minimum Fireplace Clearances

If Installed at Floor Level

Figure 9 - Minimum Fireplace Clearances

Above Combustible Flooring

Figure 7 - Minimum Mantel Clearances

When Using Hood

Minimum Non-
Combustible
Material

Minimum Non-
Combustible
Material Height

Distances to
Underside of
Mantel

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf

12"

(A)

18"

20"

22"

24"

All minimum
distances are
in inches

Log Set
All Models

2

1/2

"

6"

8"

10"

14"

Min.

Combustible

Material

Noncombustible Material

Hearth

5"

Min.

Combustible

Material