Installation – Desa CDR3924NT User Manual

Page 9

Advertising
background image

www.desatech.com

9

113183-01D

INSTALLATION AND CLEARANCES
FOR VENT-FREE OPERATION

WARNING: Maintain the

minimum clearances. If possible,

provide greater clearances from

floor, ceiling and adjoining wall.

LOG SIZING REQUIREMENTS

Log

Minimum Firebox

Size

Height

Depth Front Rear *

Width Width

24"

17"

14"

28"

20

1

/

4

"

Minimum Firebox with Blower

24"

17"

14"

34"

22

3

/

8

"

* Measured at 14" depth.
Carefully follow the instructions below. This will

ensure safe installation into a masonry, UL127-listed

manufactured fireplace or listed vent-free firebox.
Minimum Clearances For Side Combustible
Material, Side Wall and Ceiling
A. Clearances from the side of the fireplace

cabinet to any combustible material and wall

should follow diagram in Figure 4.

Example:

The face of a mantel, bookshelf,

etc. is made of combustible material and

protrudes 3

1

/

2

" from the wall. This combus-

tible material must be 4" from the side of the

fireplace cabinet (see Figure 4).

Note:

When installing your gas logs into

a manufactured firebox, follow firebox

manufacturerʼs instructions for minimum

clearances to combustible materials.

B. Clearances from the top of the fireplace opening

to the ceiling should not be less than 42 inches.

INSTALLATION

Continued

Figure 4 - Minimum Clearance for

Combustible to Wall

*Minimum 16 inches from Side Wall

*

Example

Figure 5 - Heat Resistant Material (Slate,

Marble, Tile, etc.) Above Fireplace

Minimum Noncombustible Material
Clearances

If Not Using Mantel

Note:

If using a mantel proceed to If Using Mantel.

If not using a mantel, follow the information on

this page.

You must have noncombustible material(s) above the

fireplace opening. Noncombustible materials (such as

slate, marble, tile, etc.) must be at least 1/2 inch thick.

With sheet metal, you must have noncombustible

material behind it. Noncombustible material must

extend at least 8" up. If noncombustible material is

less than 12", you must install the fireplace hood ac-

cessory. See Figure 5 for minimum clearances.

If Using Mantel

You must have noncombustible material(s) above

the fireplace opening. Noncombustible materials

(such as slate, marble, tile, etc.) must be at least

1/2 inch thick. With sheet metal, you must have

noncombustible material behind it. Noncombus-

tible material must extend at least 8 inches up.

If noncombustible material is less than 12", you

must install the fireplace hood accessory. Even if

noncombustible material is more than 12", you may

need the hood accessory to deflect heat away from

your mantel shelf. See Figure 5 and Figures 6 and

7, page 10, for minimum clearances.
IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open.

Noncombustible

Requirements for

Material Distance (A) Safe Installation
12" or more

Noncombustible material

okay.

Between 8"

Install fireplace hood

and 12"

accessory (GA6050,

GA6052 or GA6053 see

Accessories, page 25).

Less than 8"

Noncombustible material

must be extended to at

least 8". See Between 8"

and 12", above. If you

cannot extend material,

you must operate heater

with flue damper open.

Advertising