14. SAT III Controller Installation Guide

WCC III Technical Guide

14-22

SAT III Binary Input Wiring

The new WCC3 Binary Input w/ time delay board provides a terminal point for landing wire for an external input switch / relay contact. It can interface
to the SAT II or SAT III controller via a 16 pin ribbon cable with “DIP” connectors on both sides. Connect “J1 - “SAT II Connect” on the
WCC3 Binary Input w/ Time Delay Board to one of the two removable DIP SWITCHES on the cover of the SAT II or SAT III controller. These two
switches are labeled Binary Inputs on the cover of the SAT II or SAT III controller. Or an alternative method of connection to only the SAT III
controller is provided by the 6 pin HSS communications port on the side of the SAT III controller. This HSS communications port does not exist on the
SAT II controller.

The eight Binary Inputs on the new WCC3 Binary Input w/ Time Delay Board are dry contact closures to ground only.
There is an 8 position time delay switch on the new WCC3 Binary Input w/ time delay board. This time delay switch determines how long the input will
Stay on after a momentary switch contact is applied to the input of the new WCC3 Binary Input w/ time delay Board.

With the time delay dipswitch (1 to 4) all OFF, there is no delay ON for all eight inputs.
Time Delay dipswitch # 1 - (15 MIN) ON there is a 15 minute delay ON for all eight inputs.

Time Delay dipswitch # 2 - (30 MIN) ON there is an

1

hour delay ON for all eight inputs.

Time Delay dipswitch # 3 - (1 HOUR) ON there is a 1 hour delay ON for all eight inputs.
Time Delay dipswitch # 4 - (2 HOUR) ON there is a 2 hour delay ON for all eight inputs.
Time Delay dipswitch # 5 - (3 HOUR) ON there is a 3 hour delay ON for all eight inputs.
Time Delay dipswitch # 6 - (4 HOUR) ON there is a 4 hour delay ON for all eight inputs.
These Dipswitch settings are additive. With Time Delay dipswitch (1 - 15 MIN, 2 - 30 MIN, and 3 - 1 HOUR) ON there is a 1 hour and 45 minute delay
ON for all eight inputs. The eight LEDs marked BIN1 to BIN8 follow the Time Delay set by the Time Delay dipswitch #1 to # 6.

time delay board via a PCC cable.

time delay board via a PCC cable.
You should never have both Time Delay dipswitch # 7 & # 8 ON at the same time. One or the other but not both.

Note:

Communications to the WCC3 Binary Input w/ Time Delay Board Via the SAT III Controller's HSS communications port. The HSS connectors are meant
to be daisy chained with each HSS expansion board having two HSS connectors on it.

The eight input status LEDs on the new WCC3 Binary Input w

ime

elay

oard

/ T

D

B

will not stay lit during a time delay when it is

Connected to the SAT III via the HSS port.

This Binary Input board power requirements are 24 VAC and it draws 5 VA.

To the SAT III controller.
When ordering the WCC3 Binary Input w/ Time Delay Board, you must specify the length of the HSS cable at the time of the order.
PCC-01 (Power and Communications Cable - 1 foot long)
PCC-1.5 (Power and Communications Cable - 1

½ Foot long)

PCC-03 (Power and Communications Cable - 3 feet long)
PCC-25 (Power and Communications Cable - 25 feet long)
PCC-40 (Power and Communications Cable - 40 feet long)
PCC-80 (Power and Communications Cable - 80 feet long)
PCC-120 (Power and Communications Cable - 120 feet long)
PC-01 (Power Only Cable - 1 foot long)

INSTALLATION GUIDE

WCC3 HSS BINARY INPUT WITH TIME DELAY BOARD

WATTMASTER PART # OE431-01 (SS5006)

Time Delay dipswitch #7 - (L1-8) Selects Binary Inputs 1 to 8. Is used only when the SAT III HSS port is connected to the WCC# Binary Input w/

Time Delay dipswitch #8 - (L9-16) Selects Binary Inputs 9 to 16. Is used only when the SAT III HSS port is connected to the WCC# Binary Input w/

These Time Delay dipswitches #1 to #6 are ignored when the Binary Input w/time delay board is connected via the HSS port with an HSS cable (WM
Part # PCC-XX, with XX

01, 1.5, 03, 25, 40, 80, 120

). This cable provides both Power and

meaning how long the cable is in feet, available options are feet

There are 16 independent time delays on the Binary Input screen of the WCC III front-end software, one for each of the 16 binary inputs.

The 24VAC power connection is through P1 or P2 and you must observe polarity when connecting the special supplied power cable (WM part # PC-01)

WCC3 BINARY IN W/ TIME DELAY

WATTMASTER CONTROLS, INC