Sat iii, Sat iii introduction – WattMaster WCC III part 15 User Manual

Page 3

Advertising
background image

14-1

14. SAT III Controller Installation Guide

WCC III Technical Guide

SAT III Introduction

SAT III General Specifications:

The SAT III controller is a drop-in replacement for the older SAT II line of controllers that WattMaster Controls
manufactured from 1983 to 2006. The SAT III is an advanced product improvement over the SAT II controller.

The SAT III features the following:
8 Analog Inputs with 12 bit resolution (The SAT II originally had an 8 Bit A to D converter later upgraded to 10 Bit.)
8 Analog Outputs with 8 bit resolution (The SAT II also had an 8 Bit D to A converter.)

16 Relay Outputs that are Normally Open Relays with varistors for electrical noise suppression. (The SAT II used

expensive "chipswitches" that were low current output, and would only pass AC voltage and they did not have
varistors on the output for electrical noise suppression.)

16 Binary Inputs that are isolated from the microprocessor bus . These Binary Inputs are for use with an external

Binary input board.
(The older SAT II required an Isolation board. The new SAT III does not require a separate isolation board.)

For further details on the SAT III inputs and outputs - See the "SAT III - I/O Specifications" on page 3.

The SAT III communications:
It is a proprietary RS-485 based protocol, and it is based on packetized data in pre-defined parameter blocks.
Troubleshooting of the SAT III RS-485 communications loop is possible with a Digital Volt Meter.
(The SAT II was based on Manchester encoded data and was very reliable but was hard to troubleshoot.)

For the WCC III system, WattMaster Controls has developed a new isolated 485 communication bus that can support
239 SAT III's on four separate communications channels.
A single channel can support up to 60 SAT IIIs on one communications loop. This is for redundant operation. If for

some unknown reason a WCC III communications channel loop goes down, it does not cause other SAT III controllers
on the other loops to lose communications.

8

7

SAT ADDRESS

2

1

4

8

A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

WattMaster Controls Inc.

BINARY
INPUTS

BINARY
INPUTS

L8

ON OFF

128

32
16

64

L4
L3
L2

L1

L6
L5

L7

L11

L12

ON OFF

L10

L9

ON OFF

L15

L16

L14
L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF

PULSE INPUT

OPTION 1

TEST

OPTION 3

OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.

CURRENT
INPUT

THERMISTOR
INPUT

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

0 - 10V

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

PROGRAMMABLE CONTROLLER

SAT III

1

2

3

4

5

6

1

2

3

4

5

6

+V SENSORS

R1

R2

1

2

R3

R4

R5

R6

3

4

5

6

C

7

8

C

H

V

OUT

GN

D

7

8

R

R7

R8

7

8

AT

MADE

IN

TH
E

U

S

A

K1
6

K1
5

K1
4

K1
3

V16

V15

V14

V13

SAT III CONTROLLER - OE421-01

INSTALLATION GUIDE (SS5003)

Advertising