Wavetronix Click 223 (dual-485 surge protector) (CLK-223) - Quick-reference Guide User Manual

Installer quick-reference guide, Wire earth ground, Mount the device

Advertising
background image

Click 223 Dual-485 Surge

INSTALLER QUICK-REFERENCE GUIDE

2

Wire earth ground

All Click 223 devices must be grounded. To ground the device:
1 Connect a grounding wire (14 AWG) from one of the screw terminals marked PE (protective earth) to

a grounded location—for instance, to a lug bolt , if there is one on the cabinet for grounding, or to an

earth ground terminal block.

2 Make sure that the lug bolt or earth ground terminal block is grounded.

For additional security, ground the DIN rail that the Click 223 is mounted on:
1 Connect the grounding wire from the DIN rail to a grounded location—for instance, if there is a lug

bolt on the cabinet for grounding, or to an earth ground terminal block.

2 Connect another grounding wire from there to earth ground.

www.wavetronix.com

801.734.7200

1

Mount the device

The Click 223 mounts over a T-bus for power and communication:
1 If the Click 223 was shipped with the T-bus connector attached,

remove the connector from the module.

2 Snap the connector onto the DIN rail by positioning it over the

rail with the male connector pointing to the right. Hook one arm

over the edge of the DIN rail and press down on the other arm

until it snaps into place.

3 Connect the T-bus connector to the rest of the T-bus by sliding

them together until you hear them snap into place.

4 Mount the Click 223 onto the DIN rail: position it properly over

the T-bus connector, hook the lip over the lower edge of the DIN

rail, and use a rocking motion to snap the module into place.

Advertising