Rs-232, Rs-422, Rs-485 – Westermo Lynx-x08-F2G-S2 User Manual

Page 11

Advertising
background image

11

6643-2220

RS-232

Position

Signal

Direction

Description

No. 1

DSR

Out

Data Set Ready

No. 2

DCD

Out

Data Carrier Detect

No. 3

DTR

In

Data Terminal Ready

No. 4

SG

Signal Ground, not chassis ground

No. 5

RD

Out

Receive Data

No. 6

TD

In

Transmit Data

No. 7

CTS

Out

Clear To Send

No. 8

RTS

In

Request To Send

RS-422/485 (for more details see below)

Position

Signal

Direction Description

RS-422

(4-wire)

RS-485

(2-wire)

No. 1

T+

T+/R+

Out/In

RS-422: Transmit

RS-485: Transmit/Receive

No. 2

T–

T–/R–

Out/In

RS-422: Transmit

RS-485: Transmit/Receive

No. 3

R–

In

RS-422: Receive

No. 4

Not used

No. 5

Not used

No. 6

R+

In

RS-422: Receive

No. 7

Not used

No. 8

Not used

Lynx DSS is equipped with internal termination that is configurable through software
in RS-422/485 mode. The following termination schemes are supported:

RS-422

No termination

Rx

Terminate Rx

Terminate Tx

Tx

Rx

Tx

Rx

Tx

Rx

Tx

Terminate Tx and Rx

RS-485

No termination

Termination

When the unit is powered-off or during reboot, any internal termination will be
disconnected from the signal lines.
Note: Due to that the port is configurable for both RS-232 and RS-422/485,
there are no fail-safe biasing available for RS-422/485 signals.