Westermo TD-23 User Manual

Page 11

Advertising
background image

11

6600-2204

RS-422/485
Electrical specification

EIA RS-485
2-wire or 4-wire twisted pair

Data rate

300 bit/s – 1200 bit/s

Data format

7 or 8 data bits, Odd, even or none parity, 1 or 2 stop bits;

Σ 9-12 bits

Protocol

Transparent

Retiming

No

Turn around time

4.2 ms (half duplex)

Transmission range

≤ 1200 m, depending on data rate and cable type (EIA RS-485)

Settings

120 Ω termination and failsafe biasing 680 Ω

Protection

Installation Fault Tolerant (up to ±60 V)

Isolation to

Power / Leased Line

Connection

Detachable screw terminal

Connector size

0.2 – 2.5 mm² (AWG 24 – 12)

Shielded cable

Not required*

RS-232
lectrical specification

EIA RS-232

Data rate

300 bit/s – 1200 bit/s

Data format

7 or 8 data bits, Odd, even or none parity, 1 or 2 stop bits;

Σ 9-12 bits

Protocol

Transparent

Retiming

No

Transmission range

15 m

Isolation to

Power / Leased Line

Connection

9-pin D-sub female (DCE)
or Detachable screw terminal (DCE)

Connector size

0.2 – 2.5 mm² (AWG 24 – 12)

Shielded cable

Not required*

Conductive housing

Isolated to all other housings

* Railway installation close to the rails.

For a cable located inside 3 m boundary and connected to this port, the use of shielded cable is recommended,
this is to minimise the risk of interference. The cable shield should be properly connected (360°) to an earthing
point within 1 m from this port. This earthing point should have a low impedance connection to the conductive
enclosure of the apparatus cabinet, or similar, where the unit is built-in. This conductive enclosure should be
connected to the earthing system of an installation and may be directly connected to the protective earth.