=Termination

TD-23

Slave unit

Slave unit

Slave unit

TD-23

Slave unit

Slave unit

Slave unit

Max 0.3 metre

=Termination

T+
T–

T+

T-

T+

T-

A

B

R+
R–
T+
T–

R– R+

R+

T–

T–

B’ A’ B A

T+

T+ R–

2-wire termination

4-wire termination

Termination recommendations
The RS-422/485 line must be terminated. In the TD-23 the termination is combined with
fail-safe functionality. For that reason it is important that the termination is used not to
get undefined states when the bus is in three state condition.
… At 2-wire RS-485 both ends shall be terminated at the other most units of the bus.
… At 4-wire RS-485 both pairs shall be terminated at both ends.
… At 4-wire RS-422 it is only necessary to terminate the receivers.

RS-422/485 connection pins can be differently named. For some brands the T+
corresponds to A, but other brands might use some other naming convention.
If a unit does not work it can help to swap A and B.

RS-422/485 general advice