Dip-switch settings, Before dip-switch settings, S1 dip-switch selection of transmission level – Westermo TD-23 User Manual

Page 16

Advertising
background image

16

6600-2204

S1 DIP-switch
Selection of transmission level

ON

1 2 3 4 5 6 7 8

–10 dBm

ON

1 2 3 4 5 6 7 8

–12 dBm

ON

1 2 3 4 5 6 7 8

–9 dBm

ON

1 2 3 4 5 6 7 8

–13 dBm

ON

1 2 3 4 5 6 7 8

–15 dBm

DIP-switch settings

Before DIP-switch settings:

Prevent damage to internal electronics from electrostatic discharges (ESD)
by discharging your body to a grounding point (e.g. use of wrist strap).
NOTE DIP-switch alterations are only effective after a power on.

!

ON

1 2 3 4 5 6 7 8

3 dBm

ON

1 2 3 4 5 6 7 8

–3 dBm

ON

1 2 3 4 5 6 7 8

–6 dBm

S1

S2

S3

Selection of transmission level specifies the maximum output power level. The maximum value is 3 dBm. By
selecting the higher transmission levels communication over longer distances can be achieved, but the noise
and disturbance levels will increase. We recommend that you try your system with the factory default setting
first. If disturbances are detected (faulty characters or other errors) decrease the power level step by step.
If the transmission fails because of a weak signal the transmission level can be increased step by step until a
satisfactory transmission quality is achieved. Please note that levels above –9 dBm are not allowed on PTT
networks and can only be used on private wires!