3 derating diagram, Derating diagram – SMA CBL-DC-CMB1-10 User Manual

Page 13

Advertising
background image

CBL-DC-CMB1-10

106183_en_00

PHOENIX CONTACT

13

5.3

Derating diagram

The current per string must be decreased as shown in the derating diagram below, depend-

ing on ambient temperatures higher than +45°C. For each +1°C temperature increase, the

current per string must be decreased with 0,24A. The calculated derating is 1,5 % per +1°C,

in relation to the nominal current.

Ambient temperature in °C

Figure 5-1

Current per string

Current per string

16,0

14,8

13,6

12,4

8,0

9,0

10,0

11,0

12,0

13,0

14,0

15,0

16,0

17,0

18,0

45

50

55

60

Cu

rr

en

t p

e

r s

tr

in

g

i

n

A

Advertising