7.1

Servicing with the power supply disconnected

Visual inspection of cabling and components

–

Check the CBL-DC-CMB1-10 for visible damage. Only operate the device in a fault-free

state that ensures operational reliability.

–

Check all components, cables, terminal points, conductor connections, and markings

regularly and compare these to the circuit diagram and associated documentation.

–

Check the strain relief of the cables.

–

Check that all cable glands are fixed securely and sealed.

–

Check the cable routing and bending radii.

–

Check the cables, cable connections, and components for signs of overheating, e.g.,

discoloration or deformation. Replace any affected components and cables where nec-

essary. The source/trigger of overheating must be identified before the device can be

started up again and returned to a safe condition.

–

Check the tightening torques of all connections.

Tighten any loose connections taking into account the maximum torque (see „Torques

for conductive connections“).

–

Check all connections for a secure fit and correct functioning.

–

Perform this check at least once a year.

–

Parts and components that are subject to frequent use/loads must be checked at short-

er intervals.

Housings and seals

–

Check the housing for visible damage and corrosion.

–

Remove any soiling. Refer to the information in the Cleaning section.

–

Check that the housing doors lock correctly and also check the function of the lock.

–

Check that the doors open and close correctly. If necessary, lubricate the hinges.

–

Check that the housing is sealed and ensure that there is no condensation in the interi-

or.

–

All seals must be maintained at regular intervals to ensure that the housing offers the

appropriate degree of protection.

–

Check the seals for deformation, cracks, and soiling.

WARNING: Dangerous contact voltage

–

Before carrying out any servicing work on the device, disconnect the power.

–

With load break switch:

Turn the load break switch to position „0 OFF“. This interrupts the DC current of

the CBL-DC-CMB1-10.

–

Without load break switch:

Disconnect the DC circuit at the inverter. This interrupts the DC current of the

CBL-DC-CMB1-10. Please note the instructions in the manual of the manufac-

turer.

–

Open the fuse holder of the fuse modular terminal blocks in the CBL-DC-CMB1-

10 to disconnect the corresponding string current.

Warning: Never open the fuse terminal blocks under load.

–

Check the fuses and replace them when necessary.

–

All servicing work must only be carried out by qualified personnel who are familiar

with the necessary safety precautions.