CBL-DC-CMB1-10

22

PHOENIX CONTACT

106183_en_00

7.1

Servicing with the power supply disconnected

Visual inspection of cabling and components

Check the CBL-DC-CMB1-10 for visible damage. Only operate the device in a fault-free

state that ensures operational reliability.

Check all components, cables, terminal points, conductor connections, and markings

regularly and compare these to the circuit diagram and associated documentation.

Check the strain relief of the cables.

Check that all cable glands are fixed securely and sealed.

Check the cable routing and bending radii.

Check the cables, cable connections, and components for signs of overheating, e.g.,

discoloration or deformation. Replace any affected components and cables where nec-

essary. The source/trigger of overheating must be identified before the device can be

started up again and returned to a safe condition.

Check the tightening torques of all connections.

Tighten any loose connections taking into account the maximum torque (see „Torques

for conductive connections“).

Check all connections for a secure fit and correct functioning.

Perform this check at least once a year.

Parts and components that are subject to frequent use/loads must be checked at short-

er intervals.

Housings and seals

Check the housing for visible damage and corrosion.

Remove any soiling. Refer to the information in the Cleaning section.

Check that the housing doors lock correctly and also check the function of the lock.

Check that the doors open and close correctly. If necessary, lubricate the hinges.

Check that the housing is sealed and ensure that there is no condensation in the interi-

or.

All seals must be maintained at regular intervals to ensure that the housing offers the

appropriate degree of protection.

Check the seals for deformation, cracks, and soiling.

WARNING: Dangerous contact voltage

Before carrying out any servicing work on the device, disconnect the power.

With load break switch:

Turn the load break switch to position „0 OFF“. This interrupts the DC current of

the CBL-DC-CMB1-10.

Without load break switch:

Disconnect the DC circuit at the inverter. This interrupts the DC current of the

CBL-DC-CMB1-10. Please note the instructions in the manual of the manufac-

turer.

Open the fuse holder of the fuse modular terminal blocks in the CBL-DC-CMB1-

10 to disconnect the corresponding string current.

Warning: Never open the fuse terminal blocks under load.

Check the fuses and replace them when necessary.

All servicing work must only be carried out by qualified personnel who are familiar

with the necessary safety precautions.