Technical Documentation

SB2800i-11:FE0504

SMA Regelsysteme GmbH

31

6

Technical Documentation

6.1 Data PV Generator Connection

Max. input open-circuit voltage

U

PV 0

600 V (at -10 °C Module Temperature)

Input voltage, MPP operation

U

PV

224 V ... 600 V DC

Max. input current

I

PV max

13,5 A

Max. input power

DC

max

3000 W

Recommended P

PV

max. generator power

3750 Wp

All-pole disconnector
on DC input side

Multi-Contact

®

plug connector (standard - other

snap cable connectors optional)

Surge voltage protection

thermally monitored varistors

Voltage ripple

U

PP

< 10 % of input voltage

Personnel protection

Ground Fault monitoring (Riso > 1 M

)

Internal consumption in operation

< 7 W

Pole confusion prevention

by short-circuit diode

6.2 Data grid connection

Nominal output power

P

ACnom

2500 W

Peak output power

P

ACmax

2800 W

Nominal output current

I

ACnom

11 A

Harmonic distortion of output (with
K

Unom

< 2 %, P

AC

> 0,5 P

ACnom

)

THD

IAC

< 4 %

Operating range, grid voltage

U

AC

190 ... 260 V AC

Operating range, grid frequency

f

AC

49.8 ... 50.2 Hz

All-pole disconnector on grid side

independent disconnection device (MSD),
(2 independant systems)

Phase difference
(related to basic wave of current)

ϕ

Overvoltage category

III

Test voltage (50 Hz)

1.4 kV (1/5 s unit / type test)

Surge voltage test

4 kV (1.2/50 ms)
(serial interface: 6 kV)

Internal consumption in stand-by

0.25 W