Failure Code

Description

dZac-Bfr
dZac-Srr

The rate of change of the AC grid impedance is exceeding the permissable
range. („ Bfr“ or „ Srr“ is an internal message and is not important for the user.)
The Sunny Boy assumes that the public grid is down and disconnects from the
grid in order to avoid islanding.

If you therefore often observe „ dZac-Bfr“ or „ dZac-Srr“ consult the utility
company and ask if it is permissable to change the grid monitoring parameters
of the Sunny Boy. Contact SMA about how to change the grid monitoring
parameters of your Sunny Boy.

Riso

The electric isolation of the PV system to the ground is leaking. The resistance
between one of the poles and ground is below a defined threshold.

Have the plant checked for ground faults. This can be defective cable crimpings,
cracked modules (especially when moist) or similar.

Imax

Overcurrent on the AC side. This failure code is indicated in case the current to
the AC grid exceeds the specification. Have your plant configuration checked.

UpvMax

PV input voltage above the tolerable maximum value

NUW-Mess
NUW-FAC
NUW-UAC
NUW-ZAC

Internal measurement comparison error: The Sunny Boy 2800i measured values
of BFR and SRR are too different from each other.

K1-Schliess
K1-Trenn

Relay test failed

EEPROM

Transition failure during reading or writing of data EPROM, the data is not
essential for safe operation - this failure does not effect performance.

EEPROM dBh Data EPROM defective, device is set to permanent disable due to the fact that the

data loss affects important functions of the Sunny Boy. Contact SMA.

Offset

Grid monitoring self-test failed.

Rechner

BFR or SSR controller failure

ROM

The internal test of the Sunny Boy Control system firmware failed. Contact SMA
in case you observe this failure often.

Watchdog

Internal Watchdog function triggered

Iac-DC-Offs

DC injection to high

EeRestore

One of the two data records of the EEPROM was defective and has been repaired
without loosing data.