6.4.3 Sunny Boy 2800i Operating Parameters

Name Unit

Range

Default

Description

E_Total

kWh

0 ... 200000

Total energy yield (E_Total) and total operating hours
(h_Total) of the inverter. Changing the value can be
necessary when a Sunny Boy is exchanged and you
wish to match the previously acquired data

h_Total

h

0 ... 200000

Usoll-Konst

V

250 ... 600

600

PV setpoint voltage for constant voltage operation. The
parameter is only important in case the parameter
„ Betriebsart“ is set to „ U-konst“

I-NiTest/
impedance test

mA

0 ... 15000

9000

Activates (9000) and deactivates (0) the automatic
impedance measurement. This parameter only takes
effect when the Sunny Boy was deactivated (by
disconnecting from the AC utility) or set to operating
mode „ Stop“

Uac-Min/Vac-Min

V

180 ... 300

198

Lower (Uac-Min) and upper (Uac-Max) limit of
permissible AC voltage (Anti-Islanding)

Uac-Max/Vac-Max

V

180 ... 300

260

Fac-Delta-

Hz

0 ... 4.5

0.19

Maximal frequency above (Fac-Delta+) and below
(Fac-Delta-) 50 Hz grid frequency before anti-islanding
trips

Fac-Delta+

Hz

0 ... 4.5

0.19

dFac-MAX

Hz/s

0.005 ... 4.0

0.25

Maximal „ rate of change of frequency“ before
anti-islanding trips

dZac

mOhm

0 ... 2000

350

Maximal „ rate of change of grid impedance“ before
anti-islanding trips

Upv-Start

V

250 ... 600

300

Minimum voltage the Sunny Boy needs in order to
initiate normal operation.

T-Start

s

5 ... 300

10

Parameter relevant for start time. Counts seconds after
minimum PV voltage is exceeded

T-Stop

s

1 ... 1800

2

Parameter relevant for the MPP-tracking. Do not
change.

Betriebsart/
Operating Mode

MPP/Ikonst/
UKonst/Stop

MPP

Operating Mode of the Sunny Boy:
MPP: Maximum Power Point
Ukonst: Constant Voltage Mode (Setpoint defined in
„ Usoll-Konst“)
IKonst: Experimental mode / special applications
Stop: Disconnection from utility, no operation

Speicherfunktion/
Memory Function

none

Default Parameter: Sets all parameters to default
Reset Betriebsdaten: Sets all parameters that are visible
in user level to default values.
Reset Fehler: Resets a permanent device disable (dBh)

Default

GER/ENS Used for adjusting the parameters country specific

settings

Table 6.1: Operating Parameters of the Sunny Boy 2800i (changeable)

Any unauthorized modifications of the operating parameters can
1. Result in serious injuries or casualties due to altered
internal safety precautions within the Sunny Boy
2. Void the operating permission of the Sunny Boy
3. Void the warranty of the Sunny Boy
Never change the operating parameters without explicit
permission and instructions!