The Sunny Boy 3300TL is designed for 230 V grids. The voltage should be within
198 V and 260 V and the frequency should be within 49.8 Hz and 50.2 Hz. All set-
tings shown below are based on the German standard DIN VDE 0126. You are also
able to use other settings.

Limits for AC output

Voltage range

198 V ... 260 V

Frequency range

49.8 Hz ... 50.2 Hz

Voltage range

(without anti-islanding)

180 V ... 260 V

Frequency range

(without anti-islanding)

45.5 Hz ... 54.5 Hz