7.4 Sunny Boy 3800 Operating Parameters

The parameters with a grey background are only visible when in installer mode.

Any unauthorized modifications of the operating parameters can

• result in serious injuries or casualties due to altered internal

safety precautions within the Sunny Boy

• void the operating permission of the Sunny Boy
• void the warranty of the Sunny Boy.

Never change the operating parameters without explicit permis-
sion and instructions!

Name Unit

Range

Default

Betriebsart/
Operating Mode

MPP/

Ikonst/

UKonst/

Stop

MPP

Default

GER/ENS

dFac-MAX

Hz/s

0.005 ... 4.0

0.25

dZac-MAX

mOhm

0 ... 2000

350

E_Total

kWh

0 ... 200000

Fac-Delta-

Hz

0 ... 4.5 (0.19)

0.19

Fac-Delta+

Hz

0 ... 4.5

0.19

h_Total

h

0 ... 200000

Inst.-Code

NiTest/
impedance test

0 / 1

1

Riso-Min

kOhm

1000 ... 30000

1000

Speicherfunktion
Memory Function

Default parameter/

Reset Operating Data/

Reset Failure

none

Speicher/
Storage

permanent/

volatile

permanent

Uac-Min/
Vac-Min

V

180 ... 300

198

Uac-Max/
Vac-Max

V

180 ... 300

260

Usoll-Konst /
Vconst-Setpoint

V

0 ... 750

290