7.4 Sunny Boy 3800 Operating Parameters
The parameters with a grey background are only visible when in installer mode.
Any unauthorized modifications of the operating parameters can
• result in serious injuries or casualties due to altered internal
safety precautions within the Sunny Boy
• void the operating permission of the Sunny Boy
• void the warranty of the Sunny Boy.
Never change the operating parameters without explicit permis-
sion and instructions!
Name Unit
Range
Default
Betriebsart/
Operating Mode
MPP/
Ikonst/
UKonst/
Stop
MPP
Default
GER/ENS
dFac-MAX
Hz/s
0.005 ... 4.0
0.25
dZac-MAX
mOhm
0 ... 2000
350
E_Total
kWh
0 ... 200000
Fac-Delta-
Hz
0 ... 4.5 (0.19)
0.19
Fac-Delta+
Hz
0 ... 4.5
0.19
h_Total
h
0 ... 200000
Inst.-Code
NiTest/
impedance test
0 / 1
1
Riso-Min
kOhm
1000 ... 30000
1000
Speicherfunktion
Memory Function
Default parameter/
Reset Operating Data/
Reset Failure
none
Speicher/
Storage
permanent/
volatile
permanent
Uac-Min/
Vac-Min
V
180 ... 300
198
Uac-Max/
Vac-Max
V
180 ... 300
260
Usoll-Konst /
Vconst-Setpoint
V
0 ... 750
290