SMA SB 3300TL Installation User Manual

Page 35

Advertising
background image

SMA

Technologie AG

Exchanging Varistors

Installation Guide

SB3300TL-11:SE2006

Page 35

If you have found neither a ground fault nor a defective varistor there is probably a
fault in the Sunny Boy 3300TL. Please contact the SMA hotline in this case to discuss
further proceedings.

9.

If no replacement varistors are available on site
the Sunny Boy 3300TL can also be operated
without them for a limited period of time. To this
end remove the varistors you have found to be
defective and equip the terminals with a wire
jumper between terminals 2 and 3 instead. The
Sunny Boy 3300TL is then not protected against
surge voltages!

For a limited period of time a defective

varistor can be replaced by a wire

between terminal 2 and 3.

The input port thus modified is no longer protected against surge
voltages! Equip the inverter with varistors again as soon as possib-
le. The Sunny Boy 3300TL should not be operated without varistors
in plants where is a high risk of surge voltages!

10. Reconnect the PE plug to the lid and close the

Sunny Boy 3300TL again.

11. Connect the faultless string of the PV panel.

12. Switch on the circuit breaker.

13. Check whether the LEDs of the Sunny Boy

3300TL show trouble-free operation.

1 2 3

+ -

On!

Off