Sizing of a Circuit Breaker

Installation Guide

SB3300TL-11:SE2006

Page 37

9 Sizing of a Circuit Breaker

Required data of the used inverters:

• max. output current: 16 A
• max. permissible rating of the circuit breaker for one inverter: 25 A

The type of cable as well as the type of cable installation and several other conditions
have influence on the maximum rating of the circuit breaker for the inverter.

• In this example we assume that the cable used (4 mm²) can be used for nominal

currents up to 25.2 A in this example.

Selection of the circuit breakers:

• The maximum possible nominal current of the cable used and the maximum pos-

sible rating for the inverter now define the maximum possible nominal current of
the circuit breakers.

• 25 A are possible in our example for one inverter.

The circuit breakers must also be selected according to their thermal characteristics.

Example for the sizing of a circuit breaker for the AC line of a photovoltaic in-
verter for utility interaction in terms of temperature.

Photovoltaic plant with 9 inverters type Sunny Boy 3300TL with 3 inverters per
phase