2 installation – Yaskawa DC Power Input Σ-V Series User Manual

Page 15

Advertising
background image

2 Installation

E-13

2 Installation

Observe the Installation instructions in DC Power Input

Σ

-V Series User’s

Manual Setup Rotational Motor (SIEP S800000 80).

For installation sites, use proper care with the following notes.

Situation

Notes on Installation

When installed in a control

panel

• Design the control panel size, unit layout, and cool-

ing method so that the surrounding air temperature

of the SERVOPACK does not exceed 55

°C.

• When installing multiple SERVOPACKs side by

side in a control panel, install cooling fans and pro-

vide sufficient space around each SERVOPACK to

allow cooling by fan and natural convection.

When installed near a heat-

ing unit

Suppress radiation heat from the heating unit and a

temperature rise caused by convection so that the sur-

rounding air temperature of the SERVOPACK does

not exceed 55

°C.

When installed near a

source of vibration

Install a vibration isolator underneath the SERVO-

PACK to prevent it from receiving vibration.

When installed in a place re-

ceiving corrosive gases

Corrosive gases do not immediately affect the SER-

VOPACK but will eventually cause SERVOPACK or

contactor-related devices to malfunction. Take appro-

priate action to protect against corrosive gases.

Others

• Avoid installation in a hot and humid place or where

excessive dust or iron powder is present in the air.

• Be sure there is no condensation or freezing.

• Keep the surrounding air temperature 45

°C or less

to ensure long-term reliability.