Startup Procedure

There are no special procedures beyond setting parameters P1-06 and P1-07 to the correct voltage range. The
default settings are for 480-volt drives.


Changed Factory Parameters


New Defaults.
B1-03 = 1

Coast to Stop

– Recommended setting

C1-01 = 5.0

Accel Time 1

– Controls the acceleration rate when the speed reference is increased

C1-02 = 25.0

Decel time 1

– Lower set point of the deceleration OVP rate

C1-03 = 0.5

Accel time 2

– Used as the acceleration rate during speed regulation

C1-04 = 0.5

Decel time 2

– Used as the deceleration rate during speed regulation and stopping

C1-06 = 100.0

Decel time 3

– Upper set point of the deceleration OVP rate

C2-01 = 0.0

S Curve at start of accel – S curve should be off in this software

C2-02 = 0.0

S Curve at end of accel – S curve should be off in this software

C2-03 = 0.0

S Curve at start of decel – S curve should be off in this software


Custom software Parameters

New Program Group

Group P

OV Prevention


New Program Function

Function P1

OV Parameters