New Program Parameters

P1-01

DC Filter Rise amount per scan

B

B B B

DC Filter Rise

P1-01= 0.01 Vdc


The DC Filter Rise amount will be added to the DC bus filter when the DC bus voltage
exceeds the value of the DC bus filter + P1-03: Deadband. This value will be added at
a rate of 20 times a second. Using the default value results in a rate of 0.20 Vdc per
second.

P1-02

DC Filter Fall amount per scan

B

B B B

DC Filter Fall

P1-02= 0.50 Vdc


The DC Filter Fall will be subtracted from the DC bus filter when the DC bus voltage is
below the value of the DC bus filter - P1-03: Deadband. This value will be subtracted at
a rate of 20 times a second. Using the default value results in a rate of 1.00 Vdc per
second.

P1-03

DC Filter Deadband amount

B

B B B

Filter Deadband

P1-03= 10.0 Vdc


The dead band is the +/- amount that the DC bus must change before the DC bus filter
will be changed. This parameter provides a means of preventing OVP corrections for
normal DC bus fluctuations.

Setting Range:

0.00 to 1.00 Vdc

Factory Default:

0.01

Modbus Address:

0x580

Setting Range:

0.00 to 1.00 Vdc

Factory Default:

0.50

Modbus Address:

0x581

Setting Range:

0.0 to 99.0 Vdc

Factory Default:

10.0

Modbus Address:

0x582