P1-07
Over Voltage Prevention Decel Stop
Voltage
B
B B B
OVP Dec Stop
P1-07= 750 Vdc
The OVP Deceleration Stop is the DC bus level where the deceleration rate will be set
to C1-06. It may be used to control the rate of the deceleration rate’s change.
Recommended settings for different voltage units:
230 VAC – P1-07 = 350 VDC
480 VAC – P1-07 = 750 VDC
575 VAC – P1-07 = 1000 VDC
New Monitors
U1-50
Soft Starter Frequency
B
B B B
Soft Start Freq.
0.00 Hz
Displays the value of frequency coming out of the soft starter algorithm.
U1-51
DC Bus Filter Value
B
B B B
DC Bus Filter
620.0 Vdc
Displays the value of the DC bus filter.
U1-52
DC Bus Overshoot Voltage
B
B B B
DC Bus Overshoot
0.0 Vdc
Displays the difference between the value of the DC bus filter and actual DC bus
voltage.
Setting Range:
200 to 1200 Vdc
Factory Default:
750
Modbus Address:
0x586
Range:
0 to 400.00 Hz
Modbus Address:
0x00d0
Range:
0 to 1200.0 Vdc
Modbus Address:
0x00d1
Range:
0 to 1200.0 Vdc
Modbus Address:
0x00d2