Soft start freq. 0.00 hz, Dc bus filter 620.0 vdc, Dc bus overshoot 0.0 vdc – Yaskawa G5 OV Suppression User Manual

Page 7

Advertising
background image

Date: 07/01/04, Rev: 04-07

Page 7 of 8

TM.G5SW.017


P1-07

Over Voltage Prevention Decel Stop
Voltage

B

B B B

OVP Dec Stop

P1-07= 750 Vdc


The OVP Deceleration Stop is the DC bus level where the deceleration rate will be set
to C1-06. It may be used to control the rate of the deceleration rate’s change.

Recommended settings for different voltage units:
230 VAC – P1-07 = 350 VDC
480 VAC – P1-07 = 750 VDC
575 VAC – P1-07 = 1000 VDC



New Monitors


U1-50

Soft Starter Frequency

B

B B B

Soft Start Freq.

0.00 Hz


Displays the value of frequency coming out of the soft starter algorithm.

U1-51

DC Bus Filter Value

B

B B B

DC Bus Filter

620.0 Vdc


Displays the value of the DC bus filter.

U1-52

DC Bus Overshoot Voltage

B

B B B

DC Bus Overshoot

0.0 Vdc

Displays the difference between the value of the DC bus filter and actual DC bus
voltage.

Setting Range:

200 to 1200 Vdc

Factory Default:

750

Modbus Address:

0x586

Range:

0 to 400.00 Hz

Modbus Address:

0x00d0

Range:

0 to 1200.0 Vdc

Modbus Address:

0x00d1

Range:

0 to 1200.0 Vdc

Modbus Address:

0x00d2