LED Status Indicators and Diagnostics

LED Display

PWR

MS

NS

WD

Content

Cause

Solution

# The drive is not powered

# Check the drive main circuit wiring
# Turn power on

Off Off Off Off

Power

Off

# The option board is not connected

correctly or securely to the drive

# Turn Off drive power
# Check the connection of the option board to the 2CN

connector on the drive

# Turn power on

Solid

Green

Off

Off

Solid Red CPU Fault

# The option board CPU is being

initialized or has a fault

# Cycle power to the drive
# If the fault persists, replace the option board

Solid

Green

Flashing

Green

Off

Flashing

Green

Option Board
Initialization

# Option board Initialization

# Wait for initialization to complete
# If initialization does not complete within several

seconds, cycle power to the drive

# If initialization does not complete after power cycling

the drive, replace the option card

Solid

Green

Flashing

Red

Off

Flashing

Green

Recoverable Option
Board Fault

# An incorrect DIP switch setting or

other recoverable fault

# Check baud rate setting (DIP switches DR1 and DR0),

then cycle power to the drive

# If the fault persists, replace the option board

Solid

Green

Solid Red

Off

Flashing

Green

Unrecoverable Option
Board Fault

# An un-recoverable fault

# Cycle power to the drive
# If the fault persists, replace the option board

Solid

Green

Solid Red Solid Red

Flashing

Green

Baud Rate Setting Fault # DR1 and DR0 are both set to ON

# Set the baud rate switches correctly
# Cycle power to the drive

Solid

Green

Solid

Green

Flashing

Red

Flashing

Green

Communication
Timeout

# A master communication timeout

# Check network termination
# Check network wiring
# Check that the communication bus wiring is separated

from the main circuit wiring

Solid

Green

Solid

Green

Solid Red

Flashing

Green

Communication Error

# Unrecoverable communication fault

# Check that other device’s MAC ID is not unique per

the network

# Check that the master is configured correctly
# Check that the end termination resistors are correctly

connected to the communication bus

# Check that the communication device is correctly

connected per wiring diagrams

# Check that the communication bus wiring is separated

from the main circuit wiring

Solid

Green

Solid

Green

Flashing

Green

Flashing

Green

Normal Not
Communicating

# Connected to a DeviceNet network

but not communicating

# Send explicit message or I/O message from the master

as necessary

Solid

Green

Solid

Green

Solid

Green

Flashing

Green

Normal
Communicating

# Connected to a DeviceNet network

and communicating normally

-

Note: 1: Do not install remove or handle a network card connected to the drive with power applied to the drive. Remove power from the drive and wait for the charge lamp to be

completely extinguished. Wait at least five additional minutes for the drive to be completely discharged. Measure the DC BUS voltage and verify that it is at a safe level.

2: When cycling power to the drive make sure that the drive is fully discharged prior to reapplying power.