Figure 10 Remove the NEMA Type 1 Conduit Bracket

(Models BA0001F to BA0003F and 2A0001F to 2A0006F)

8.

On models (BA0001F to BA0003F and 2A0001F to 2A0006F), the screw for the drive
ground terminal also acts as one of the screws that attaches the NEMA Type 1 conduit
bracket to the drive. Reattach the NEMA Type 1 conduit bracket according to Figure
27 and connect the drive-side of the ground wire to the drive ground terminal.

Note:

The different ground wires packaged with the option connect the option to different drive

models. Select the proper ground wire depending on drive size. Refer to

Table 5

on page

20

for ground wire selection by drive model.

Ground terminal

Ground wire

Drive ground terminal/
NEMA Type 1 conduit
bracket screw

Ground wire

Drive-side
connector
Screw size:
M3.5 to M6

Option unit
connector
Screw size: M3

Figure 11 Reattach the NEMA Type 1 Conduit Bracket and Connect the Ground Wire

(Models BA0001F to BA0003F and 2A0001F to 2A0006F)

5 Installation Procedure

22

YASKAWA TOEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Installation Manual