Option Error Codes

n

Option Fault Monitors U6-98 and U6-99

The option can declare error/warning conditions via drive monitor parameters on the drive

digital operator as shown in

Table 11

.

Table 11 Option Fault Monitor Descriptions

Fault

Condition

Fault Declared

Status Value

(U6-98/U6-99)

Description

No Fault

n/a

0

No faults

Force Fault

EF0

3

Network sent a message to force this node

to the fault state.

Connection

Timeout

BUS ERROR

1101

The control connection timed out.

Duplicate IP

Address

BUS ERROR

1102

This node and at least one other node have

the same IP Address.

Default MAC

Address

None

1103

Factory default MAC Address

programmed into the option. Return for

reprogramming.

Network Link

Down

BUS ERROR

1104

No network link to option.

Hardware Error

BUS ERROR

1105

Option card hardware has stopped

functioning. Cycle power to the drive.

Two drive monitor parameters, U6-98 and U6-99 assist the user in network troubleshooting.
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared

upon drive power-up.

• U6-99 displays the present option status. U6-99 is cleared upon a network-issued fault reset

and upon power-up.

If another fault occurs while the original fault is still active, parameter U6-98 retains the

original fault value and U6-99 stores the new fault status value.