3 circuits and wiring specifications – Yaskawa VARISPEED-600 SERIES INVERTER User Manual
Page 30

31
3.3 CIRCUITS AND WIRING SPECIFICATIONS
Table 2
Circuits and Wiring Specifications
Name
Circuit
Termi-
nals
Wire
Size
AWG
(mm
2
)
Wire Type Terminal
Screw
Max.
Torque
lb⋅in
(N⋅m)
Braking Unit
(Models CDBR
2015B 2022B
Main
¨
¨
0
©
©
0
12−10
(3.5−5.5)
M4
13.3
(
−2015B, −2022B,
−4030B, −4045B,
−5037B)
Con-
trol
1 2 3
4 5 6
18−14
(0.75−2)
M4
13.3
(1.50)
Braking Unit
(Model CDBR
Main
¨
¨
0
©
©
0
10−8
(5.5−8) 600V
M5
21.7
(2.45)
(Model CDBR
−2045B, −4090B,
−5110B)
Con-
trol
1 2 3
4 5 6
18−14
(0.75−2)
600V
(High
Voltage)
*3
vinyl
M4
15.6
(1.76)
Braking Unit
(Model
CDBR 2110B
Main
¨
¨
0
©
©
0
4 (22)
8−6
(8−14)
*1
vinyl
sheathed
wire or
equivalent
M6
43.4
(4.90)
(
CDBR−2110B,
−4220B,−5300B)
Con-
trol
1 2 3
4 5 6
18−14
(0.75−2)
equivalent
M4
15.6
(1.76)
Braking Resistor
Unit
Main
B
P
12−10
(3.5−5.5)
M4
(M5)
*2
15.6 (1.76)
(21.7(2.45))
(Model LKEB−
j
)
Con-
trol
1
2
18−14
(0.75−2)
M4
15.6 (1.76)
*1 For wire size of 8−6 (8−14), use UL1283 heat−resistant vinyl−insulated wire or
equivalent.
*2 M4 for Models LKEB−20P7 to −27P5 or −40P7 to −4015.
M5 for Models LKEB−2011 to −2022 or −4018 to −4045.
*3 Models−5037B, −5100B, and −5300B can reach an operating voltage of 1040 VDC.
Please select wire which is suitable for the operating voltage.