5. TROUBLESHOOTING

Only authorized personnel should be permitted to perform maintenance and inspec-
tions or replace parts.

No.

Fault Status

Cause

Corrective Action

Braking resistor

:

Without braking unit

Inverter built−in main circuit dis-

charging transistor short circuited

Replace the inverter.

1

Braking resistor

unit overload

relay (or thermal

overload protec-

t ) t i

h

t

:

With braking unit

Braking unit main circuit discharging

transistor short circuited

Replace the unit.

p

tor) trips when not

decelerating.

Improper braking unit power supply

voltage selection connector setting
(Power supply voltage > power sup-

ply voltage selection position)

Set it again.

2

Inverter trips at

Insufficient braking resistor unit ca-

pacity

Examine the braking

conditions again.

2

Inverter trips at

overvoltage (OV). Improper wiring

Check and repair.

overvoltage (OV).

Braking unit fault

Replace the unit.

3

Braking resistor

unit overload

relay (or thermal

protector) some-

times trips.

Insufficient braking resistor unit ca-

pacity

Examine the braking

conditions again.

Braking unit trips

Excessive start/stop switching fre-

quency

Examine the operat-

ing conditions again

4

Braking unit trips

by heat sink over-

Excessive load inertia

ing conditions again.

4

by heat sink over-

heat.

Improper combination of braking

unit and braking resistor unit

Reset.

Ambient temperature 104EF (40EC)

Reduce it.