Yaskawa V7 High HP User Manual

Page 3

Advertising
background image

Date: 03/29/05, Rev: 05-03

Page 3 of 8

TM.V7SW.026H

2. Modifications from standard software

Changed item

High frequency software

Standard software

Maximum output frequency

800Hz

400Hz

Carrier frequency

Fixed at 5kHz

Parameter n080 (Carrier
frequency selection) deleted

2.5kHz ~ 10kHz, synchronous
carrier, selected by parameter
n080

Setting unit for all parameters related to
frequency
Frequency reference and output frequency
display units

Fixed at 0.1Hz.

Parameter n035 (Setting/display
unit of frequency reference
selection) is deleted

0.01Hz (less than 100Hz)

0.1Hz (above 100Hz)

Selected by parameter
n035

Memobus frequency reference/monitor unit

selection

n152 selection 1 (0.01Hz) is deleted

This selection is included

Control mode

Fixed at V/f mode

Parameters for VVC mode are
deleted

V/f or VVC

Set by n002 (Control
mode selection)

Torque compensation

n103 (Torque compensation gain)
setting unit is 0.01

n103 setting unit is 0.1

V/f setting

Parameter n045 (Base frequency
voltage) added

No base frequency voltage
parameter

Deleted functions*

Frequency reference unit
selection

Control mode selection

Carrier frequency selection

Slip compensation

Energy savings

Input/output phase loss detection

Dynamic braking resistor
overheat protection

Reference loss detection

Multi-function analog input
(operator CN2)

PID control

Pulse output monitor

These functions are included

* Please refer to the deleted parameter list on the following page

Advertising