4. Function explanation

(1) Maximum output frequency

The maximum output frequency is 800Hz.


(2) Carrier frequency

The carrier frequency is fixed at 5kHz.
There is no parameter to set the carrier frequency (n080 in standard software).


(3) Setting unit for frequency related parameters

Fixed at 0.1Hz.
There is no parameter to change the setting/display unit (n035).
(Soft starter internal calculation resolution is 0.001Hz).


(4) Display unit for frequency reference/output frequency monitors

Fixed at 0.1Hz.
There is no parameter to change the setting/display unit (n035).


(5) Memobus frequency reference/monitor unit

It is possible to select 0.1Hz/1, 100%/30000 and 0.1%/1 by parameter n152.
0.01Hz/1 (n152 = 1 in standard software) cannot be set.


(6) Control mode

Control mode is fixed at V/f.
Parameters related to VVC are removed.
• The deleted parameters are shown below.

Control mode selection (n002), Overtorque detection function selection 2 (n097), Motor leakage
inductance (n108), Torque compensation voltage limit (n109), Slip compensation during
regenerative operation (n113).


(7) Torque compensation

The amount of torque compensation is decreased proportionally to output frequency as follows.








The amount of torque compensation is a percentage of parameter n103 (Torque compensation gain).







120Hz 160Hz

Output Frequency

Amount of torque

compensation

100%