Yaskawa iQpump1000 AC Drive User Manual

Iqpump1000 ac drive simplex quick start procedure, Page 1 of 4, Improper wiring can and will cause

Advertising
background image

Step

1

iQpump Model

Identification and Mounting

Connect Motor and

Line Power

Step

2

Step

4

Step

3

Page 1 of 4

WARNING DO NOT CONNECT ANY OF THE

FOLLOWING TERMINALS TO EARTH GROUND

B1

B2

-

+1

+2

+3

NOT USED

Fig.1 & 2

below show the electrical connections for the input

power and motor terminals for various iQpump models.

Select

the proper diagram for the model you are installing

(see Step

1).

WITH POWER OFF

make the appropriate connections.

Make sure to follow good wiring practices and all applicable
codes. Ensure that the equipment is grounded properly as
shown in fig. 1

DANGER;

LETHAL VOLTAGES ARE PRESENT- Before

applying power to the iQpump, ensure that the terminal cover
is fastened and all wiring connections are secure. After the
power has been turned OFF, wait at least five minutes until
the charge indicator extinguishes completely before touching
any wiring, circuit boards or components.

!

Make sure the iQpump has been properly sized for single phase input
power. For best performance, the drive input supply voltage must be
equal to or greater than the motor rated voltage.

3Ø Induction

motor

Connect
frame to

ground

Input

Protection

(Fuse or Circuit

Breaker)

To change direction of motor

rotation swap any

two of the

three motor leads.

Fig. 2 Input Power and Output Motor Electrical Connections for
Models: 2_0110 & Larger and 4_0058 & Larger

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to

chassis
ground

Use L1, L2, L3 for

3Ø Input Power

L1 L2 L3

Use L1, L2 for

1Ø Input Power

*

BUS TERMINALS:
DO NOT CONNECT TO GROUND

Use L1, L2, L3 for

3Ø Input Power

To change
direction of

motor rotation
swap any

two

of the

three

motor leads.

Fig. 1 Input Power and Output Motor Electrical Connections for
Models: 2_0004 - 2_0056, 4_0002 - 4_0044 and 5_0003 - 50011

Use L1, L2 for

1Ø Input Power

3Ø Induction

motor

Connect
frame to

ground

Input

Protection

(Fuse or Circuit

Breaker)

L1 L2 L3

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to chassis

ground

*

DC Bus terminals
location varies by

model.

*

To make sure you received the correct model, it is essential to

verify the iQpump nameplate with your order and make sure

the iQpump has the correct rating so it can be used with your

motor. Please check the nameplate information as shown in

the example below.

·

Check that the available power will meet the

input power

requirements.

·

Ensure that the

output power from the iQpump is

compatible with the motor requirements.

Mounting the iQpump

·

In the case of systems with more than one iQpump, follow
the above procedure for each iQpump and motor.

The mounting of the iQpump is extremely important
regarding environment and accessibility. Depending on your
system, there are various models available and the mounting
dimensions (footprint) may be different. Because the
mounting procedure is fairly extensive, it is beyond the scope
of this document; the user is referred to the iQpump Quick
Start Guide (Document No. TOEP YAIP1W 01) received with
the iQpump, S

Section 2.2 Mechanical Installation. Match the

model that you received and follow the procedure described
in the manual to ensure a safe and functional installation. In
cases where the system has more than one iQpump, refer to
the proper clearances required for adequate ventilation.
Please pay particular attention to:

·

The clearances to be maintained around the enclosure
for adequate ventilation.

·

The environmental specifications such as avoiding
excessive dampness, extreme temperatures, chemical
exposure, corrosive areas, etc. to avoid damage to the
equipment and to maintain safety.

Removing and Attaching the Terminal Cover

Improper removal of the iQpump terminal cover as well as
front cover can cause extensive damage to the iQpump. To
avoid damage to these items, please pay particular attention
to the iQpump Quick Start Guide, Document No. TOEP
YAIP1W 01, S

Section 3.5, Removing and Attaching the

Terminal Cover.

Open Chassis

NEMA 1

Drive Model

Number

Input Power

Rating

Output Power

Rating

Serial

Number

UL File

Number

Drive Spec Number

Weight

Software

Version

Normal

Duty Amps

CIMR-PW2A0021FAA
CIMR-PW2A0021FAA

CC :

8000

6W3050 - 2 - 100

J0073D207410100

This step shows how to connect control wiring and feedback signal to the iQpump. Before
making any control connections M

MAKE SURE POWER TO THE iQpump IS TURNED OFF!

Next remove the terminal cover to gain access to the control terminals. (Step 1.)

SELECT START / STOP CONTROL METHOD

b1-02

NOTE: It is beyond the scope of this document to program the iQpump drive for network communication control.
Please refer to the refer to the iQpump Quick Start Guide, (Document No. TOEP YAIP1W 01) for this selection.

FEEDBACK SIGNAL WIRING (TRANSDUCER)

Wiring Diagram: 2-Wire Control

Run

(FWD)

Wiring Diagram: 3-Wire Control

Use for momentary contacts

Use for maintained contacts

User Terminals

User Terminals

Note: 3

rd

row of terminal board is shown here.

Link

Start

Switch

Stop

Switch

Normally

Open

Normally

Closed

Link

+V AC

A1 A2

A3 FM AM AC RP AC 24V

Brown or Red: +Power (1)

Black: Output
4 – 20mA (2)

Cable
Shield

+V AC

A1 A2

A3 FM AM AC RP AC 24V

2-Wire, 4-20mA Transducer

Cable

Type

DIN

Type

E(G)

S1 S2

S3 S4

S5 S6

S7

S8

SN SC SP

S1 S2

S3 S4

S5 S6

S7

S8

SN SC SP

Install link (AC-SN) when
using transducer.

SN

Factory Installed

To use 3-Wire Control first Initialize the
iQpump using parameter A1-03 = 3330
(Refer to the Quick Start Guide
TOEP YAIP1W 01)

For use with 3-Wire, 0 – 10V Transducer

Brown or Red: +Power (1)

Black or White Output 0 – 10V (3)

Blue or Black Common Signal (2)

Important Note: Signal colors and numbering may vary depending on
feedback device used, please consult feedback device manual.

!

The iQpump is D

DEFAULT SETUP TO START/STOP FROM THE KEYPAD (digital operator).

If this is the preferred start/stop method then continue to the feedback signal connection
section. Please refer to the wiring diagram below to start/stop the iQpump using an external
switch or contact.

For use with 2-Wire, 4 – 20mA Transducer

(Factory Default)

E(G)

(Factory Default)

Jumper located

inside the drive on
the terminal board

Note: 2

nd

row of terminal

board is shown here.

A1 A3

A2

V

I

Set Jumper to use 0 – 10V

Transducer

Jumper located

inside the drive on
the terminal board

Note: 2

nd

row of terminal

board is shown here.

A1 A3

A2

V

I

3-Wire, 0-10V Transducer

Selecting Start/Stop and Speed Method

Real-time

Clock Setup

The following
procedure is a
supplement to
other
documentation
supplied with this
equipment and
will guide the user
in properly wiring
the iQpump and
motor. It will also
show the user
how to configure
the iQpump for a
simplex pump
application.

DANGER!

Improper wiring
can and will cause

bodily harm as
well as damage to
the equipment.

When installing
the system be
sure to follow
good wiring
practices and all
applicable codes.
Ensure that the
mounting of the
various
components are
secure and that
the environment,
such as extreme
dampness, poor
ventilation etc. will
not cause system
degradation.

Please read this
cheat sheet and
other
documentation
provided with the
iQpump
thoroughly before
attempting any
installation.

This step shows how to setup the
iQpump real-time clock for first
use.

Note: If clock is not set the drive
can still be programmed and
operated, but ALM light will flash
every 30s and showing C

Clock Not

Set message.

Power up the drive and set the
real-time Clock. The real-time
Clock setup screen will appear at
first power up.

Press to set the clock.

Note: After the real-time clock is
set the real-time clock setup
screen will not show again unless
parameter o4-17 is set to “Set”.

Real-time Clock Setup Screen

Use to move cursor to

The left and to move

cursor to the right

use to adjust.

When date and time are set

press to save.

Note: Do NOT adjust sec per
month.

Example:

Jun 12

th

2012, 7:35am

Yaskawa America, Inc., 2121 Norman Drive South, Waukegan, IL 60085, (800) YASKAWA (927-5292) Fax (847) 887-7310, [email protected], www.yaskawa.com, Document Number: TM.TM.iQp1000.01 03/25/2013 © Yaskawa America, Inc.

iQpump1000 AC Drive
Simplex Quick Start Procedure

Advertising