Motor Rotation Test

In this step the motor is checked for proper direction and operation. This
test is to be performed solely from the digital operator. Apply power to the
iQpump after all the electrical connections have been made and protective
covers have been re-attached. At this point, D

DO NOT RUN THE MOTOR,

the Digital Operator should display as shown in

Fig. 3.

Fig. 3: Digital Operator

Use precaution, and refer to

Fig.1 or 2, swap any two of the
three output leads to the motor
(U/T1, V/T2 and W/T3). After the
wiring change, repeat

Step 8

and recheck motor direction.

After the power has been turned OFF, wait at least five minutes until the
charge indicator extinguishes completely before touching any wiring, circuit
boards or components.

DANGER

!

Digital Operator

turned off.

Verify feedback on display (show keypad) matches mechanical pressure
gauge.

FEEDBACK SIGNAL CHECK

FEEDBACK SIGNAL LEVEL

Refer to parameter P1-02 and P1-03, if the
feedback device scaling or system units are
incorrect.

Next, push

and the HAND

LED should be

ON.

The motor should now be operating at in the correct direction of pump.

Push

on the Digital Operator; the display should read

on the Digital Operator; the display should read as in Fig. 3.

No alarm active

Auto Mode Off

Hand Mode Off

If the direction is not correct, then power down the iQpump and follow

Instructions below.

Press to access Hand Speed. Use to change

Hand Speed value. Press to save value.

Step

8

Pump Rotation and Feedback Signal Check

Step

9

Auto Mode Operation

AUTO MODE

Press the A

AUTO button to put the iQpump into AUTO mode.

In AUTO mode the iQpump is capable of starting or stopping based on the Run Source
Selection setting parameter b1-02. (See Step 3 Select Start/Stop Control Method) The
setpoint used in AUTO mode is based on the Reference Source Selection setting
parameter b1-01. (See Step 3 Select Speed Method)

The iQpump can be operated in AUTO mode when the following actions have been
performed:
·

All parameters are programmed

·

Motor direction has been checked

·

Auto Mode: Reference source selected in parameter b1-01 (See step 3)

·

Auto Mode: Run source selected in parameter b1-02 (See Step 3)

Next, press

to access or modify the system setpoint that was entered using

SET SYSTEM SETPOINT

iQpump automatically starts in Auto Mode when the feedback signal level falls below
the programmed level in parameter P1-04 for the specified time in P1-05.

Use

to select the digit and

to change the system setpoint.

Next press

Next, press the A

AUTO

button to start the
iQpump.

Start Pump System

Start

Delay

145 PSI

Start / Draw Down
Level P1-04

System Setpoint
(Example 80 PSI)

Feedback signal from

pressure transducer

(4 – 20 mA)

0

Pressure

Start Level Delay (P1-05)

(Example 5.0 sec.)

WAIT

to store setpoint and press

operation menu.

to return to the main

Refer to Illustration 2 on Page 3 of 4 for additional information on the Start Level Function.

parameter Q1-01 System Setpoint in the iQpump Quick Setup Menu

Example: 80 PSI

LED is blinking

when AUTO mode
is active but AUTO

Run Command is

not active.

Fig. 4: Digital Operator

Sleep and Anti-No-Flow (ANF) Detection

NOTE: Before adjusting Anti-No-Flow operation ensure your system is regulating satisfactory while operating under
normal running conditions.

If stable continue to Step 1 to verify no-flow/sleep operation. If unstable turn off the Anti-No-Flow function
(P2-23 = 0.00%) and adjust the PI control parameters b5-02 and b5-03 to stabilize pump system. Refer to iQpump
Quick Start Guide (Document No.TOEP YAIP1W 01) for additional information. Once the system is stable, re-
enable the Anti-No-Flow function by setting P2-23 to 0.40% and continue to Step 1 to verify no-flow/sleep
operation.

Step 1: Verify system holds pressure by creating a no-flow situation (e.g. close off discharge valve).

Step 2: Press OFF button on the digital operator, wait 1 min. until system stabilizes and verify system pressure
feedback U1-91. If the pressure drops more than 3 PSI (U1-91) adjust P2-25 to the actual delta pressure drop plus
1 PSI.

Example:

Setpoint is 80 PSI, pressure feedback U1-91 shows 76 PSI, P2-25 should be 4 + 1 or 5 PSI.

Note: This value should always be more than your start level (P1-04). If not, the system pressure is not holding and
this needs to be corrected, or the pump system will continue to cycle on and off.

Step 3: Run system in normal automatic operation with flow. Next check monitor
U1-99 “ANF Timer” and verify that the value is incrementing and resetting back to zero continuously. If the value
holds at 10 sec. (P2-24) increase P2-24 “Anti-No-Flow Detection Time” by increments of 5 sec. Repeat Step 3 each
time P2-24 is adjusted.

Step 4: Create a no-flow situation (e.g. close discharge valve) and monitor that U1-99 “ANF Timer” increments and
holds at P2-24 time (value set in Step 3). Once the Anti-No-Flow timer expires the speed will reduce gradually until
it reaches minimum pump speed (P1-06) where it will hold for 5 sec. (P2-03) before going to sleep.

Step 5: Run system in normal automatic operation and verify sleep and wake-up operation until system performs
satisfactory.

(P2-23, P2-24, P2-25)

The iQpump can be operated in HAND mode when the following actions have been performed:
·

All parameters are programmed

·

Motor direction has been checked

HAND MODE

Press to access Hand Speed. Use to change Hand Speed value. Press

to save value.

Set parameter P5-01 ‘Hand Mode Ref.’ to ‘0’ to adjust the hand mode reference from an external 0 – 10V signal
connected to terminal A3 and AC.

Hand Speed from Analog Input (0 – 10V)

+

0 – 10V Connection

0 ~ 10Vdc

+V AC

A1 A2

A3 FM AM AC RP AC 24V

Cable
Shield

E(G)

Step

10

Hand Mode Operation