Iqpump1000 simplex quick start procedure, Page 2 of 4 – Yaskawa iQpump1000 AC Drive User Manual

Page 2

Advertising
background image

iQpump Quick Setup Parameter Overview (Simplex)

Step

5

Changing Parameters and

Monitoring the iQpump

Step

6

Application Setup

Step

7

Page 2 of 4

This step shows how to access and modify an iQpump parameter
as well as how to monitor iQpump signals such as output
frequency and motor current.

Make sure all protective covers have been re-attached and power
is turned on. DO NOT RUN THE MOTOR.

Press two times until the digital operator shows the parameter menu.

Select Digit

Access Parameter Menu and Change Parameter Value

Monitor Motor Frequency and Motor Current

Please refer to the iQpump Quick Start Guide, (Document No.
TOEP YAIP1W 01) on how to access other drive monitors.

2X

Inc./Dec. Selection

Inc./Dec. Selection

Go to Next Digit

Switch to Edit Mode

Save New Value

Modify Value

iQpump Digital Operator power-up state

Output Frequency and Transducer Feedback can be monitored

simultaneously.

Hold button for 3 sec. to go back to the main menu.

2X

Use and to select monitor signals.

Press simultaneously shows the monitor menu.

Use to select monitor.

Press to access monitor menu.

This step shows how to configure the iQpump for a dedicated pump
application.

Make sure all protective covers have been re-attached and power is
turned on. DO NOT RUN THE MOTOR.

Available iQpump Application Macro’s:

·

6008 Constant Pressure Mode (PSI)

·

6009 Pump Down Level Mode (Ft)

·

6010 Geothermal Mode

·

6011 VTC Pressure Control Mode

·

7770 General Purpose Mode

Press two times until the digital operator shows the parameter menu.

Select Digit

Select Application

2X

Inc./Dec. Selection

Select Application

Switch to Edit Mode

Press to select.

Hold button for 3 sec. to go back to the main menu.

2X

Enter Application Parameters

3X

Select Parameter.

Switch to Edit Mode

Save New Value

Modify Value

Hold button for 3 sec. to go back to the main menu.

Go Back to Main Menu

Default

The factory default is setup for
constant pressure PSI, only change if
application different.

Yaskawa America, Inc., 2121 Norman Drive South, Waukegan, IL 60085, (800) YASKAWA (927-5292) Fax (847) 887-7310, [email protected], www.yaskawa.com, Document Number: TM.TM.iQp1000.01 03/25/2013 © Yaskawa America, Inc.

Parameter

Value

Description

Reference

Comments

A1-06

Dependent on

Initialization

Mode

Application
Selected

Displays selected applications, see Step 6.

Read-only cannot be modified

E2-01

Drive Size

Dependent

Motor Rated Cur-
rent

Set to the motor nameplate full load amps.

For submersible motors use service
factor amps (SFA).

E2-04

2

Number of Motor
Poles

Number of motor poles is used to show the correct

motor RPM on the display

Enter ’4’ for an 1800 RPM motor and ‘2’ for a 3600

RPM motor.

Confirm number of poles

2 Pole Motor = 3600 RPM

4 Pole Motor = 1800 RPM

6 Pole Motor = 1200 RPM

8 Pole Motor = 900 RPM

P1-03 145

Feedback Device
Scaling

System Scaling: Enter feedback device maximum:

Example: Enter 200 for pressure transducer with a

maximum of 200 PSI at 20mA.

Confirm feedback device scaling.

(See Illustration 1)

Q1-01

0

Setpoint 1

Set System Setpoint

Set to system pressure

P1-04

0.0 PSI

Start / Drawn
Down Level

When the iQpump is turned On and the feedback

signal level (transducer) falls below this level, the

pump system will start after the time specified in P1-

05 (default 1 sec).

Programming the Start Level as an Absolute

Value. Start / Draw Down Level has to programmed

to a positive value in order for the Start / Draw Down

Level to be an absolute value. Example: Start /

Draw Down Level P1-04 set to 50 PSI and delay

time P1-05 set to 5 sec. Pump system will start

when the pressure drops below 50 PSI for 5 sec.

Programming the Start Level as a Delta Level

from the System Setpoint

Start / Draw Down Level has to programmed to a

negative value in order for the Start Level to be a

delta value from the setpoint.

Example: Start / Draw Down Level P1-04 set to –10

PSI with a system setpoint of 50 PSI and a delay

time P1-05 set to 5 sec. Pump system will start

when the pressure drops below 40 PSI (50 - 10) for

5 sec.

It is mandatory to program the Start / Draw

Down Level in order to use the sleep func-

tion.

(See Illustration 2 and 3)

P1-06

40.0 Hz

Minimum Pump
Speed

Minimum speed (Hz) the pump motor has to operate

at. Example: Base pump motor speed is 3600 RPM,

minimum speed is 2400 RPM. Set

minimum pump frequency to 40.0 Hz. (2400 ÷ 3600

x 60 Hz = 40 Hz)

Minimum pump frequency should be set to

a value where the pump enters a no-flow

condition.

P4-10

0

Disabled

Auto Mode Opera-
tor Run Power
Down
Storage

Stores the run status in the Auto mode when operat-
ing from digital operator (b1-02=0).
0: Disabled
1: Enabled

Recommended for use when Start/Stop

command is from the keypad.

(See Step 9)

P5-04

1

Enabled

Hand Key
Enable / Disable

Enables or disables the Hand Key on the digital op-
erator.
0: Disabled
1: Enabled

Hand Key on keypad.

(See Step 10)

Use

to change the sign.

iQpump1000
Simplex Quick Start Procedure

Advertising