5 floor pedestal installation, Figure 4 floor pedestal details, Floor pedestal installation – Emerson Liebert FPC User Manual

Page 11: Figure 4, Floor pedestal details, Caution

Advertising
background image

Installation Instructions

7

1.1.5 Floor Pedestal Installation

Floor pedestals are optional equipment that provide clearance for bottom cable entry or exit for FPC

units not installed on raised flooring. The pedestals are adjustable over a limited range (approxi-

mately 3-1/2" [89mm]) to allow leveling the FPC and minor adjustments in the unit’s installed height.

1. Insert the pedestal threaded shaft into the pedestal holes in the cabinet base as shown in

Figures 1 and 2.

2. Adjust the pedestal height by turning the welded nut/shaft assembly into or out of the pedestal

base as required.

3. Lock the height by tightening the jam nut against the pedestal base.

The pedestal may be anchored to the floor by means of the four holes in the base. Locations of

floor pedestals are shown in Figures 1 and 2.

Figure 4

Floor pedestal details

!

CAUTION

Floor pedestals may be reverse-assembled for shipping. Before installation, the pedestals

should be reassembled as shown in Figure 4. When the pedestal is properly assembled, the

washer on top of the welded nut provides a bearing surface for the unit’s weight.

6"

(152mm)

square

2-1/4"

(57mm)

2-1/4"

(57mm)

2-1/4"

(57mm)

2-1/4"

(57mm)

.56" (14mm)
diameter
mounting holes

Pedestal
Base

Jam Nut

Welded Nut

Washer

Threaded
Shaft

3"

(76mm)

Advertising