Table 11 torque specifications, general, Table 11, Table 12 – Emerson Liebert FPC User Manual

Page 28: Branch circuit breaker torque specifications, Table 13, Table 14, Torque specifications, general

Advertising
background image

Equipment Inspection and Startup

24

Table 11

Torque specifications, general

Electrical connections

with 1 Belleville washer

Electrical connections

with 2 Belleville washers

Torque

Torque

lb-in

N-m lb-in

N-m

Bolt shaft size, in./mm

1/4 / M6

40

4.5

80

9.0

5/16 / M8

80

9.0

180

18.0

3/8 / M10

120

13.6

240

27.1

1/2 / M12

480

54.3

Input and output breakers
Up to 150 amp

80

9.0

160

18.0

175 - 500A

120

13.6

240

27.1

Table 12

Panelboard main circuit breaker torque specifications

Torque

lb-in

N-m

Busbar-to-breaker 240 27.1

Table 13

Branch circuit breaker torque specifications

Breaker size

lb-in

N-m

Up to 30 amp

20

4.0

40 to 100 amp

20

5.1

Table 14

Terminal block compression lug torque specifications

AWG wire size

or range

Torque

lb-in

N-m

#14 - #10

35

4.0

#8

40

4.5

Advertising