Table 5, Main input circuit breaker interrupting rating – Emerson Liebert FPC User Manual

Page 17

Advertising
background image

Installation Instructions

13

150

208

427

600

(2) 350 kcmil *

416

600

(2) 350 kcmil *

240

370

500

(2) 250 kcmil *

-

-

-

380

234

300

350 kcmil

228

300

350 kcmil

400

223

300

350 kcmil

217

300

350 kcmil

415

215

300

350 kcmil

209

300

350 kcmil

480

185

250

250 kcmil

-

-

-

600

148

200

#3/0 AWG

-

-

-

200

380

312

400

(2) #3/0 AWG *

304

400

(2) #3/0 AWG *

400

297

400

(2) #3/0 AWG *

289

400

(2) #3/0 AWG *

415

286

400

(2) #3/0 AWG *

278

350

(2) #2/0 AWG *

480

247

350

(2) #2/0 AWG *

-

-

-

600

197

250

250 kcmil

-

-

-

225

380

352

450

(2) #4/0 AWG *

342

450

(2) #4/0 AWG *

400

334

450

(2) #4/0 AWG *

325

450

(2) #4/0 AWG *

415

322

450

(2) #4/0 AWG *

313

400

(2) #3/0 AWG *

480

278

350

(2) #2/0 AWG *

-

-

-

600

222

300

350 kcmil

-

-

-

300

380

469

600

(2) 350 kcmil *

456

600

(2) 350 kcmil *

400

446

600

(2) 350 kcmil *

433

600

(2) 350 kcmil *

415

430

600

(2) 350 kcmil *

417

600

(2) 350 kcmil *

480

372

500

(2) 250 kcmil *

-

-

-

600

297

400

(2) #3/0 AWG *

-

-

-

* Parallel feeders per NEC 300-20 and 310-4
FLA = Full Load Amps of Power Center
OPD = Overcurrent Protection Device inside FPC
Wire sizes based on NEC 2005, Table 310-16, using 75°C copper conductor
1. Main input power feeder should be a dedicated feeder direct from service entrance or other power source possible
2. Ground conductors recommended to be insulated conductors run with power conductors for increased system performance. Ground

conductor minimum size per NEC Table 250-66. Input power feeder conduit may be used as the safety ground conductor. When conduit
is used, adequate electrical continuity must be maintained at conduit connections to enclosures and throughout conduit run.

3. Input feeder wire size listed in this table is the minimum feeder size recommended. Larger wire size may be required because of voltage

drop or supply overcurrent protection device.

4. For transformerless units with 3-phase 4W + G input feeder larger wire size may be required because of excessive neutral current (see

NEC Table 310-15 note 4: For best performance, the unit should be located as close to load as practical.

Table 5

Main input circuit breaker interrupting rating

Standard interrupting rating*

208V

480V

380-415V

600V

65 kA

35 kA

35 kA

18 kA

* Refer to unit specification sheet for units equipped
with non-standard main input breakers.

Table 4

Suggested minimum input wire size data (continued)

kVA

Input

Voltage

Units with Transformers

Transformerless Units

Input

FLA

Input

OPD

Suggested Feeder

Wire Size (AWG)

Full Load

Amps

MIB Trip

Amps

Suggested Feeder

Wire Size (AWG)