Figure 1

Typical cabinet and floor planning dimension data, 23" (584mm) cabinet, 15-125 kVA

Table 1

23-inch cabinet weight

Unit

kVa

Weight, lb (kg)

60Hz

50Hz

Without

Transformer

15

1010 (458)

1060 (480)

750 (340)

30

1090 (494)

1140 (517)

750 (340)

50

1160 (526)

1235 (560)

750 (340)

75

1350 (612)

1450 (658)

800 (363)

100

1540 (699)

1665 (755)

800 (363)

125

1650 (748)

1775 (805)

800 (363)

Overall Dim.
39-1/2" (1003mm)
Including hinge
and bezel
projection

Overhead clearance
of 18" (457mm)
recommended
for cooling airflow

Minimum side
clearance of 42" (1067mm)
recommended for service access
if unit is equipped with
distribution monitoring option

Shaded areas indicate
recommended clearance
of 42" (1067mm) at front and
rear for service access

For units with bottom
cable access, clearance
of 6" (152mm) below
unit is recommended
for cooling airflow
and cable entry/exit

Dia. location
3/4" (19mm)
typical

Floor Pedestals
available from
6" (152mm) to 18"
(457mm)

.56" (14mm)
diameter; 4 holes
typical

6" (152mm)

6" (152mm)

23-1/2"

(597mm)

36.4"

(925mm)

Unit Base Outline

Unit Base Outline

Optional Floor Pedestals

Shaded area indicates
cable access and
cooling airflow

Footprint and Floor

Cutout Dimensions

36.4" (925mm)

78-1/2" (1995mm)

Front

Front

23-1/2" (597mm)

1.2"

(30mm)

1.2"

(30mm)

Overall Dimension
25.2" (640mm)
including side
panels

34" (864mm)

6"

(152mm)

11-1/2" (292mm)

6" (152mm)

3.2" (81mm)

8.3"

(211mm)

Cabinet Dimensional Data

Advertising