Signal reference grid, Table 10, Minimum grounding electrode conductor size (awg) – Emerson Liebert FPC User Manual

Page 20

Advertising
background image

Installation Instructions

16

Signal Reference Grid

If the unit is used to supply power to a computer room or area that is equipped with a signal reference

grid or a grounded raised-floor stringer system, a grounding conductor should be connected from the

system ground bus to the grid or floor system. This conductor should be stranded or braided #8 AWG

or larger, and as short as practical. Less than 3 ft. (1m) is recommended.

1.3.4 Grounding Electrode Conductor for FPCs With Transformer

Required by code - The Liebert FPC with transformer must be grounded according to the safety

practices of NEC 250-26. A local grounding electrode conductor is recommended in addition to the

equipment safety ground which is normally run with the input power conductors. (See Figures 5

through 8.)
As shown in Figure 12, the grounding electrode conductor is run from the unit to the nearest effec-

tively grounded location (listed in order of preference):

• Building steel
• Metal water pipe
• Other made grounding electrode

The grounding electrode conductor’s size is based on the secondary circuit conductors. Table 10

shows the minimum recommended grounding electrode conductor according to the NEC

(Table 250-66).

Recommended methods for running the grounding electrode conductor (arranged by preference for

system performance; as acceptable by local and other applicable codes):

• Outside of conduit (where not subject to damage)
• Inside non-metallic conduit
• Inside non-ferrous conduit
• Inside ferrous conduit, bonded to the ferrous conduit at both ends, as acceptable by local and other

applicable codes

Table 10

Minimum grounding electrode conductor size (AWG)

kVA

Output Voltage

208V 380V 415V

15 8 8 8
30 8 8 8
50 4 8 8
75 2 6 6

100

0 4 4

125

0 2 2

150 00 2 2
200 00 0 0
225 00 0 0
300

00 0 0

AWG wire size based on 75°C copper conductors