Info, Reset meter to factory defaults, Heater operation – Precision Digital PD662 User Manual

Page 26

Advertising
background image

PD662 Loop-Powered Meter

Instruction Manual

26

Reset Meter to Factory Defaults

When the parameters have been changed in a way that is difficult to
determine what’s happening, it might be better to start the setup
process from the factory defaults.
Instructions to load factory defaults:
1. Enter

the

Advanced features menu. See Advanced Features Menu,

page 20.

2. Press

Up arrow button to display info menu.

3. Press

RIGHT arrow button when info is shown.

4. Press

ENTER button when rSt is shown.

Press Enter again when display flashes rSt.
Note: If Enter is not pressed a second time within three seconds,
rSt

will stop flashing and the last ENTER press cancelled.

5. The meter goes through an initialization sequence (same as on

power-up), and loads the factory default settings.

Heater Operation

Models with the integrated heater option require no additional setup. All
heater operations are controlled automatically by the unit. An internal
temperature sensor controls the operation of the heater. The heater is
only on when required due to external temperatures.

rSt

info

Press and Hold for 5 Sec

Meter Re-

Initializes

Flashing
Display

rSt

FNc