Input, Heater – Precision Digital PD662 User Manual

Page 7

Advertising
background image

PD662 Loop-Powered Meter

Instruction Manual

7

Input

ACCURACY

±1 count

FUNCTION

Linear (2 to 32 points) or square root

TEMPERATURE
DRIFT

50 PPM/

°C from -40 to 85°C ambient

DECIMAL POINT User selectable decimal point
MINIMUM SPAN

Input 1 & Input 2: 0.40 mA

CALIBRATION
RANGE

An Error message will appear if input 1 and input 2 signals
are too close together.
Input
Range

Minimum Span
Input 1 & Input 2

4-20 mA 0.40 mA

MAXIMUM
VOLTAGE DROP

Without Backlight

With Backlight

1.7 VDC @ 20 mA

3.7 VDC @ 20 mA

EQUIVALENT
RESISTANCE

85 Ω @ 20 mA

185 Ω @ 20 mA

INPUT
OVERLOAD

Over current protection to 2 A max.

Heater

POWER

24 VDC, 11 W max.

REQUIRED
SWITCH & FUSE

A CSA Approved fuse rated min 30 VDC, 1 A, T and a readily
accessible switch or a circuit breaker shall be provided to
facilitate the disconnection of power to the heater.

OPERATION
METHOD

On/Off control with an internal temperature sensor. Heater is
on only when necessary due to external temperatures.

TEMPERATURE
CUTOFF

Internal 104°C thermal cutoff for over temperature protection.

ENVIRONMENTAL
(with Heater)

Operating temperature for CSA certification: -55 to 75°C
Functional temperature range: -55 to 85°C

Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing