SERVEVIEW PRO INSTALLATION AND OPERATIONS MANUAL

28

Appendix D. Rack mount instructions
The ServeView Pro can be mounted in a rack using the Rackmount kits

from Rose Electronics.

The optional rack mount kit includes the following items:

Two black anodized mounting brackets.

Four 6-32 x 3/8” flat head mounting screws.

To rack mount your ServeView Pro, attach the two rack mounting brackets

to your unit with the short flange against the unit using the four screws

provided. Secure the mounting brackets to the rack using the appropriate

size bolts, nuts and lock washers. Using hardware other than that provided

could cause damage to the electronics and/or result in loss of mounting

integrity. Do not over tighten the screws used to mount the unit to the

mounting brackets.

The following general guidelines should be observed when installing your

unit into a rack.

1. The ServeView Pro is designed to work in an ambient temperature of

0

ο

C to 55

ο

C (32

ο

F – 131

ο

F).

2. Do not block power supply vents or otherwise restrict airflow when

rack-mounting this unit.

3. Mechanical loading of the rack should be considered to prevent

instability and possible tipping over.

4. Tighten all connectors securely and provide adequate strain relief for

all cables.

5. Provide a grounded power source to all units. Pay special attention to

overall branch circuit load ratings before connecting equipment to this

source. Overloaded circuits are potential fire hazards and can cause

equipment failures or poor performance.

Appendix E. Rack mount illustration