All installations and services must be performed by qualified service personnel.

range is between 70°F to 100°F. A lower temperature rise usually results in a higher
system efficiency.

:

If the temperature rise exceeds 100°F, the heat exchanger may fail, voiding

the heat exchanger warranty resulting in property damage, personal injury or loss of
life.


M. FLUE GAS COMBUSTION ANALYSIS

:

Burner adjustments must be confirmed by instrumentation. Failure to use

accurate or calibrated instrumentation to correctly setup the burner may result in
reduced efficiency, sooting, and/or the production of hazardous carbon monoxide gas.

For typical burner combustion analysis results, refer to the table below.

BURNER COMBUSTION PARAMETERS

FURNACE MODEL

OMD-70

GMD-85

FUEL TYPE

#1 OR #2 FUEL OIL

NATURAL GAS

PROPANE GAS

CO (CARBON MONOXIDE)

50PPM OR LESS

50PPM OR LESS

50PPM OR LESS

CO2 (CARBON DIOXIDE)

11-12%

8.75-10%

9.5-11%

O2 (OXYGEN)

4.5-6%

5.9-3.8%

6.7-4.5%

SMOKE SPOT RATING

0 TO TRACE

N/A

N/A

AIR SHUTTER

ADJUSTMENT

OPEN TO

POSITION 35

OPEN TO

POSITION 4

OPEN TO

POSITION 4

N/A = NOT APPLICABLE