Thermo Pride OMD-70 User Manual

Page 40

Advertising
background image

All installations and services must be performed by qualified service personnel.

39

Does the circulating air

blower turn off after

thermostat is satisfied

within 4 minutes?

Does burner shut off

when thermostat is

satisfied?

Has the high limit thermostat

or auxiliary high limit

thermostat activated?

Check all wiring for

loose connections.

Yes

Yes

Yes

Yes

No

No

Yes

No

No

Check for reduced airflow through

the furnace. This may be caused

by an excessively restrictive duct

system, an inadequate amount of

supply air,especially for furnaces

installed in closets, or extremely
dirty air filters. Also, check and

confirm heat input rate to unit is

within specifications.

Does system run until

thermostat is satisfied?

Check fan timer settings

against those on connection

diagram. Is fan selector

switch set on "manual".

Reset if necessary. Does

fan still fail to turn off?

Replace fan timer.

Yes

Check for short in wire

to thermostat. Replace

thermostat, if necessary.

Troubleshooting Complete.